Mining CablesCables
AS/NZS 2802 Type 450 Mining Cable
General use cable for mines (except for underground coal mines). It has smaller dimensions but strong structure.
3.3/3.3 kV, 6.6/6.6 kV, 11/11 kV, 22/22 kV

General use cable for mines (except for underground coal mines). Suitable to trailing and reeling due to its’ smaller dimensions.
General use cable for mines (except for underground coal mines). Suitable to trailing and reeling due to its’ smaller dimensions.
| Rated voltage | 3.3/3.3 kV, 6.6/6.6 kV, 11/11 kV, 22/22 kV |
|---|---|
| Conductor | Electrolytic, multiple-stranded circular flexible tinned copper wire (rope lay) AS/NZS 1125-2.10 |
| Insulation | XR-EP-90 (Class 1, acc. to AS/NZS 3808) (Earth cores are not insulated) |
| Outer sheath | Extra heavy-duty elastomer outer sheath (acc. to AS/NZS 3808) |
| Separator | Semiconducting layer over earth conductors |
| Separator | Semiconducting layer |
| Screen | Semiconductive elastomer screen over phase cores. |
| Layup | All phase cores are laid up in contact with each other. Two ground cores and one pilot core are laidup in beetween. |
| Bedding | Semiconducting elastomeric compound |
| Separator | Open weave braid for reinforcement |
| Related standards | AS/NZS 2802 |
| Test voltage | 12 kV, 22 kV, 30 kV, 45 kV |
| Power cores | Pilot and earth cores | Sheath | Mass | |||||||
|---|---|---|---|---|---|---|---|---|---|---|
| Cross section mm2 | Bülüm no/mm | Conductor diameter Nom. mm | Insulation thickness mm | Insulation diameter Nom. mm | Stranding no./mm | Insulation thickness mm | Thickness mm | overall diameter Nom. Mm | Approximate weight kg/km | Copper weight kg/km |
| Tip | 455.3 | 3.3/3.3kV | Class 1 | insulation | ||||||
| 35 | 285/0.40 | 8.5 | 2.2 | 15.2 | 114/0.30 | 1.4 | 4.8 | 46.7 | 3.35 | 1.242 |
| 50 | 380/0.40 | 10 | 2.4 | 17.1 | 171/0.30 | 1.4 | 5.3 | 51.9 | 4.25 | 1.789 |
| 70 | 203/0.67 | 12 | 2.4 | 19.1 | 51/0.67 | 1.4 | 5.7 | 57 | 5.55 | 2.535 |
| 95 | 259/0.67 | 13.2 | 2.4 | 20.3 | 70/0.67 | 1.6 | 6.1 | 60.5 | 6.45 | 3.448 |
| 120 | 336/0.67 | 15.3 | 2.4 | 22.4 | 84/0.67 | 1.6 | 6.4 | 65.6 | 7.85 | 4.312 |
| 150 | 427/0.67 | 17.1 | 2.4 | 24.2 | 112/0.67 | 1.6 | 6.5 | 69.7 | 9.3 | 5.458 |
| 185 | 518/0.67 | 19.2 | 2.4 | 26.3 | 132/0.67 | 1.6 | 6.6 | 74.5 | 10.7 | 6.671 |
| 240 | 672/0.67 | 21.8 | 2.4 | 28.9 | 168/0.67 | 1.6 | 6.8 | 80.5 | 13.1 | 8.62 |
| 300 | 854/0.67 | 24.4 | 2.4 | 31.5 | 228/0.67 | 1.6 | 6.9 | 86.3 | 16 | 10.956 |
| Tip | 455.6 | 6.6/6.6kV | Class 1 | insulation | ||||||
| 16 | 126/0.40 | 5.7 | 3 | 14 | 114/0.30 | 1.4 | 4.7 | 43.9 | 2.65 | 695 |
| 25 | 209/0.40 | 7.2 | 3 | 15.5 | 114/0.30 | 1.6 | 5 | 47.8 | 3.3 | 954 |
| 35 | 285/0.40 | 8.5 | 3 | 16.8 | 114/0.30 | 1.6 | 5.3 | 51.3 | 3.85 | 1.242 |
| 50 | 380/0.40 | 10 | 3 | 18.3 | 171/0.30 | 1.6 | 5.6 | 55.1 | 4.65 | 1.789 |
| 70 | 203/0.67 | 12 | 3 | 20.3 | 51/0.67 | 1.6 | 6 | 60.3 | 5.95 | 2.535 |
| 95 | 259/0.67 | 13.2 | 3 | 21.5 | 70/0.67 | 1.8 | 6.3 | 63.5 | 6.9 | 3.448 |
| 120 | 336/0.67 | 15.3 | 3 | 23.6 | 84/0.67 | 1.8 | 6.5 | 68.5 | 8.25 | 4.312 |
| 150 | 427/0.67 | 17.1 | 3 | 25.4 | 112/0.67 | 1.8 | 6.6 | 72.6 | 9.75 | 5.458 |
| 185 | 518/0.67 | 19.2 | 3 | 27.5 | 132/0.67 | 1.8 | 6.7 | 77.3 | 11.2 | 6.671 |
| 240 | 672/0.67 | 21.8 | 3 | 30.1 | 168/0.67 | 1.8 | 6.9 | 83.3 | 13.6 | 8.62 |
| 300 | 854/0.67 | 24.4 | 3 | 32.7 | 228/0.67 | 1.8 | 7 | 89.1 | 16.5 | 10.956 |
| Tip | 455.11 | 11/11kV | Class 1 | insulation | ||||||
| 16 | 126/0.40 | 5.7 | 5 | 18.1 | 114/0.30 | 2 | 5.8 | 55.1 | 3.9 | 695 |
| 25 | 209/0.40 | 7.2 | 5 | 19.6 | 114/0.30 | 2 | 6.1 | 59 | 4.6 | 954 |
| 35 | 285/0.40 | 8.5 | 5 | 20.9 | 114/0.30 | 2 | 6.3 | 62.2 | 5.25 | 1.242 |
| 50 | 380/0.40 | 10 | 5 | 22.4 | 171/0.30 | 2 | 6.4 | 65.6 | 6.05 | 1.789 |
| 70 | 203/0.67 | 12 | 5 | 24.4 | 51/0.67 | 2 | 6.5 | 70.2 | 7.4 | 2.535 |
| 95 | 259/0.67 | 13.2 | 5 | 25.6 | 70/0.67 | 2.2 | 6.7 | 73.2 | 8.35 | 3.448 |
| 120 | 336/0.67 | 15.3 | 5 | 27.7 | 84/0.67 | 2.2 | 6.8 | 77.9 | 9.8 | 4.312 |
| 150 | 427/0.67 | 17.1 | 5 | 29.5 | 112/0.67 | 2.2 | 6.9 | 82 | 11.4 | 5.458 |
| 185 | 518/0.67 | 19.2 | 5 | 31.6 | 132/0.67 | 2.2 | 7 | 86.8 | 13 | 6.671 |
| 240 | 672/0.67 | 21.8 | 5 | 34.2 | 168/0.67 | 2.2 | 7.2 | 92.8 | 15.5 | 8.62 |
| Tip | 455.22 | 22/22KV | Class 1 | insulation | ||||||
| 16 | 126/0.40 | 5.7 | 7.6 | 23.5 | 120/0.30 | 2.5 | 6.6 | 68.5 | 5.75 | 695 |
| 25 | 209/0.40 | 7.2 | 7.6 | 25 | 120/0.30 | 2.5 | 6.6 | 71.7 | 6.5 | 954 |
| 35 | 285/0.40 | 8.5 | 7.6 | 26.3 | 120/0.30 | 2.5 | 6.7 | 74.7 | 7.15 | 1.242 |
| 50 | 380/0.40 | 10 | 7.6 | 27.8 | 183/0.30 | 2.5 | 6.8 | 78.2 | 8.1 | 1.789 |
| 70 | 203/0.67 | 12 | 7.6 | 29.8 | 54/0.67 | 2.5 | 7 | 82.9 | 9.55 | 2.535 |
| 95 | 259/0.67 | 13.2 | 7.6 | 31 | 70/0.67 | 2.5 | 7.1 | 85.7 | 10.6 | 3.448 |
| 120 | 336/0.67 | 15.3 | 7.6 | 33.1 | 84/0.67 | 2.5 | 7.2 | 90.5 | 12.2 | 4.312 |
| 150 | 427/0.67 | 17.1 | 7.6 | 34.9 | 112/0.67 | 2.5 | 7.3 | 94.6 | 13.9 | 5.458 |
| 185 | 518/0.67 | 19.2 | 7.6 | 37 | 132/0.67 | 2.5 | 7.4 | 99.3 | 15.6 | 6.671 |
Tell us your quantity and requirements — we reply within one business day.
Mining CablesGeneral use cable for mines (except for underground coal mines). It has smaller dimensions but strong structure.
Mining CablesGeneral use cable for mines (except for underground coal mines)
Mining CablesGeneral use cable for mines (except for underground coal mines)
Share your specifications and quantities. Our team will review your request and come back with sourcing options and a quotation.