Mining CablesCables
AS/NZS 2802 Type 455 Mining Cable
General use cable for mines (except for underground coal mines). Suitable to trailing and reeling due to its’ smaller dimensions.
3.3/3.3 kV, 6.6/6.6 kV, 11/11 kV, 22/22 kV

Used as flexible cable for underground coal mines where reduced bending radii is needed (except for shuttle cars)
Used as flexible cable for underground coal mines where reduced bending radii is needed (except for shuttle cars)
| Rated voltage | 1.1/1.1 kV, 3.3/3.3 kV, 6.6/6.6 kV |
|---|---|
| Conductor | Electrolytic, stranded tinned copper wire AS/NZS 1125 Class 6 |
| Insulation | Power and pilot cores are insulated with R-EP-90 (acc. to AS/NZS 3808). Earth cores not not insulated |
| Outer sheath | Heavy-duty elastomer outer sheath (acc.to AS/NZS 3808) |
| Separator | Semiconducting layer over power conductors 3.3/3.3kV and above types and over earth conductors of all types |
| Separator | Semiconducting layer over power core insulations |
| Layup | Cores are laid up over a semiconducting cradle with one pilot core in the center and without contacting each other, but in contact with interstitial earth cores |
| Bedding | Semiconducting elastomeric compound |
| Separator | Open weave braid for reinforcement |
| Related standards | AS/NZS 1802 |
| Test voltage | 4,2 kV, 12 kV, 22 kV |
| Power Cores | Earth cores | Pilot core | Sheath | Mass | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| CROSS SECTION (mm2) | Strand no/mm | Conductor Diameter Nom. mm | Insulation thickness mm | Insulation diameter Nom. mm | Strand Min.no/mm | Crosssection mm2 | Semiconductive covering thickness mm2 | Strand no/mm | Insulation thickness Min.mm | Thickness mm | Overall diameter Nom. Mm | APPX. WEIGHT (kg / km) | COPPER WEIGHT (kg / km) |
| TYPE | 245.1 | 1.1/1.1kV | |||||||||||
| 95 | 1332/0.30 | 13.9 | 2 | 18.3 | 150/0.30 | 10.6 | 1 | 28/0.25 | 0.8 | 5.6 | 60.4 | 6.3 | 3.078 |
| 120 | 1702/0.30 | 15.7 | 2.1 | 20.4 | 195/0.30 | 13.8 | 1.2 | 28/0.25 | 0.8 | 6 | 65.5 | 7.65 | 3.89 |
| 150 | 2146/0.30 | 17.6 | 2.3 | 22.7 | 235/0.30 | 16.6 | 1.2 | 28/0.25 | 0.8 | 6.3 | 70.5 | 9.15 | 4.835 |
| TYPE | 245.3 | 3.3/3.3kV | |||||||||||
| 50 | 703/0.30 | 9.7 | 3 | 16.5 | 120/0.30 | 8.5 | 1 | 28/0.25 | 0.8 | 5.7 | 56.8 | 4.9 | 1.721 |
| 70 | 988/0.30 | 11.6 | 3 | 18.4 | 180/0.30 | 12.7 | 1.2 | 28/0.25 | 0.8 | 6 | 61.2 | 6 | 2.418 |
| 95 | 1332/0.30 | 13.9 | 3 | 20.7 | 235/0.30 | 16.6 | 1.2 | 28/0.25 | 0.8 | 6.4 | 66.6 | 7.35 | 3.251 |
| 120 | 1702/0.30 | 15.7 | 3 | 22.5 | 300/0.30 | 21.2 | 1.2 | 28/0.25 | 0.8 | 6.7 | 71 | 8.7 | 4.103 |
| 150 | 2146/0.30 | 17.6 | 3 | 24.4 | 375/0.30 | 26.5 | 1.2 | 28/0.25 | 0.8 | 7 | 75.2 | 10.2 | 5.12 |
| TYPE | 245.6 | 6.6/6.6kV | |||||||||||
| 50 | 703/0.30 | 9.7 | 5 | 20.5 | 120/0.30 | 8.5 | 1.4 | 28/0.25 | 0.8 | 6.7 | 67.2 | 6.35 | 1.721 |
| 70 | 988/0.30 | 11.6 | 5 | 22.4 | 180/0.30 | 12.7 | 1.4 | 28/0.25 | 0.8 | 7 | 71.7 | 7.55 | 2.418 |
| 95 | 1332/0.30 | 13.9 | 5 | 24.7 | 235/0.30 | 16.6 | 1.4 | 28/0.25 | 0.8 | 7.4 | 77.1 | 9.05 | 3.251 |
| 120 | 1702/0.30 | 15.7 | 5 | 26.5 | 300/0.30 | 21.2 | 1.4 | 28/0.25 | 0.8 | 7.7 | 81.3 | 10.5 | 4.103 |
| 150 | 2146/0.30 | 17.6 | 5 | 28.4 | 375/0.30 | 26.5 | 1.4 | 28/0.25 | 0.8 | 8 | 85.8 | 12.1 | 5.12 |
Tell us your quantity and requirements — we reply within one business day.
Mining CablesGeneral use cable for mines (except for underground coal mines). Suitable to trailing and reeling due to its’ smaller dimensions.
Mining CablesGeneral use cable for mines (except for underground coal mines). It has smaller dimensions but strong structure.
Mining CablesGeneral use cable for mines (except for underground coal mines)
Share your specifications and quantities. Our team will review your request and come back with sourcing options and a quotation.