Mining CablesCables
AS/NZS 2802 Type 455 Mining Cable
General use cable for mines (except for underground coal mines). Suitable to trailing and reeling due to its’ smaller dimensions.
3.3/3.3 kV, 6.6/6.6 kV, 11/11 kV, 22/22 kV

General use cable for underground coal mines (except for shuttle cars)
General use cable for underground coal mines (except for shuttle cars)
| Rated voltage | 1.1/1.1 kV, 3.3/3.3 kV, 6.6/6.6 kV, 11/11 kV |
|---|---|
| Conductor | Electrolytic, multiple-stranded circular flexible tinned copper wire (rope lay) AS/NZS 1125-2.10 |
| Insulation | Power and pilot cores are insulated with R-EP-90 (acc. to AS/NZS 3808). Earth cores are not insulated |
| Outer sheath | Heavy-duty elastomer outer sheath (acc.to AS/NZS 3808) |
| Separator | Semiconducting layer over power conductors (3.3/3.3kV and oabove) and earth conductors (all) |
| Separator | Semiconducting layer over power core insulations |
| Layup | Cores are laid up over a semiconducting cradle with one pilot core in the center and without contacting each other, but in contact with interstitial earth cores |
| Bedding | Semiconducting elastomeric compound |
| Separator | Open weave braid for reinforcement |
| Related standards | AS/NZS 1802 |
| Test voltage | 4,2 kV, 12 kV, 22 kV, 30 kV |
| Power Cores | Earth cores | Pilot core | Sheath | Mass | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| CROSS SECTION (mm2) | Strand no/mm | Conductor Diameter Nom. mm | Insulation thickness mm | Insulation diameter Nom. mm | Strand Min.no/mm | Crosssection mm2 | Semiconductive covering thickness mm2 | Strand no/mm | Insulation thickness Min.mm | Thickness mm | Overall diameter Nom. Mm | APPX. WEIGHT (kg / km) | COPPER WEIGHT (kg / km) |
| Type | 241.1 | 1.1/1.1kV | |||||||||||
| 16 | 126/0.40 | 5.7 | 1.6 | 9 | 39/0.30 | 2.8 | 1 | 24/0,20 | 0.8 | 3.9 | 34.1 | 1.7 | 549 |
| 25 | 209/0.40 | 7.2 | 1.6 | 10.5 | 63/0.30 | 4.5 | 1 | 24/0,20 | 0.8 | 4.2 | 37.9 | 2.25 | 862 |
| 35 | 285/0.40 | 8.5 | 1.6 | 11.8 | 87/0.30 | 6.2 | 1 | 24/0,20 | 0.8 | 4.4 | 41.2 | 2.75 | 1.199 |
| 50 | 380/0.40 | 10 | 1.7 | 13.5 | 114/0.30 | 8.1 | 1 | 40/0,20 | 0.8 | 4.9 | 45.9 | 3.5 | 1.686 |
| 70 | 203/0.67 | 12 | 1.8 | 16 | 36/0.67 | 12.7 | 1 | 40/0,20 | 0.8 | 5.3 | 52.2 | 4.8 | 2.394 |
| 95 | 259/0.67 | 13.2 | 2 | 17.6 | 36/0.67 | 12.7 | 1 | 40/0,20 | 0.8 | 5.8 | 56.7 | 5.7 | 3.114 |
| 120 | 336/0.67 | 15.3 | 2.1 | 20 | 39/0.67 | 13.8 | 1.2 | 40/0,20 | 0.8 | 6.3 | 62.7 | 7.1 | 3.866 |
| 150 | 427/0.67 | 17.1 | 2.3 | 22.2 | 48/0.67 | 17 | 1.2 | 40/0,20 | 0.8 | 6.7 | 68.3 | 8.65 | 4.822 |
| 185 | 518/0.67 | 19.2 | 2.5 | 24.7 | 63/0.67 | 22.3 | 1.4 | 40/0,20 | 0.8 | 7.3 | 74.9 | 10.3 | 5.983 |
| 240 | 672/0.67 | 21.8 | 2.8 | 27.9 | 77/0.67 | 27.2 | 1.4 | 40/0,20 | 0.8 | 8 | 83.3 | 13 | 7.708 |
| 300 | 854/0.67 | 24.4 | 3 | 30.9 | 98/0.67 | 34.6 | 1.4 | 40/0,20 | 0.8 | 8.7 | 91.2 | 16 | 9.649 |
| Type | 241.3 | 3.3/3.3kV | |||||||||||
| 16 | 126/0.40 | 5.7 | 3 | 12.5 | 39/0.30 | 2.8 | 1 | 24/0,20 | 0.8 | 5 | 43.8 | 2.5 | 549 |
| 25 | 209/0.40 | 7.2 | 3 | 14 | 63/0.30 | 4.5 | 1 | 24/0,20 | 0.8 | 5.3 | 47.7 | 3.15 | 862 |
| 35 | 285/0.40 | 8.5 | 3 | 15.3 | 87/0.30 | 6.2 | 1 | 24/0,20 | 0.8 | 5.6 | 51.1 | 3.75 | 1.199 |
| 50 | 380/0.40 | 10 | 3 | 16.8 | 114/0.30 | 8.1 | 1.2 | 40/0,20 | 0.8 | 6 | 55.2 | 4.55 | 1.686 |
| 70 | 203/0.67 | 12 | 3 | 18.8 | 36/0.67 | 12.7 | 1.2 | 40/0,20 | 0.8 | 6.4 | 60.3 | 5.8 | 2.394 |
| 95 | 259/0.67 | 13.2 | 3 | 20 | 36/0.67 | 12.7 | 1.2 | 40/0,20 | 0.8 | 6.8 | 63.8 | 6.75 | 3.114 |
| 120 | 336/0.67 | 15.3 | 3 | 22.1 | 39/0.67 | 13.8 | 1.2 | 40/0,20 | 0.8 | 7.2 | 69.1 | 8.15 | 3.866 |
| 150 | 427/0.67 | 17.1 | 3 | 23.9 | 48/0.67 | 17 | 1.2 | 40/0,20 | 0.8 | 7.6 | 73.8 | 9.65 | 4.822 |
| 185 | 518/0.67 | 19.2 | 3 | 26 | 63/0.67 | 22.3 | 1.4 | 40/0,20 | 0.8 | 8 | 79.2 | 11.3 | 5.983 |
| 240 | 672/0.67 | 21.8 | 3 | 28.6 | 77/0.67 | 27.2 | 1.4 | 40/0,20 | 0.8 | 8.6 | 86 | 13.8 | 7.708 |
| 300 | 854/0.67 | 24.4 | 3 | 31.2 | 98/0.67 | 34.6 | 1.4 | 40/0,20 | 0.8 | 9.1 | 92.6 | 16.6 | 9.649 |
| Type | 241.6 | 6.6/6.6kV | |||||||||||
| 16 | 126/0.40 | 5.7 | 5 | 16.5 | 39/0.30 | 2.8 | 1.4 | 24/0,20 | 0.8 | 6.1 | 54.9 | 3.7 | 549 |
| 25 | 209/0.40 | 7.2 | 5 | 18 | 63/0.30 | 4.5 | 1.4 | 24/0,20 | 0.8 | 6.4 | 58.8 | 4.45 | 862 |
| 35 | 285/0.40 | 8.5 | 5 | 19.3 | 87/0.30 | 6.2 | 1.4 | 24/0,20 | 0.8 | 6.7 | 62.2 | 5.15 | 1.199 |
| 50 | 380/0.40 | 10 | 5 | 20.8 | 114/0.30 | 8.1 | 1.4 | 40/0,20 | 0.8 | 7.1 | 66.2 | 6 | 1.686 |
| 70 | 203/0.67 | 12 | 5 | 22.8 | 36/0.67 | 12.7 | 1.4 | 40/0,20 | 0.8 | 7.4 | 71.2 | 7.35 | 2.394 |
| 95 | 259/0.67 | 13.2 | 5 | 24 | 36/0.67 | 12.7 | 1.4 | 40/0,20 | 0.8 | 7.9 | 74.8 | 8.45 | 3.114 |
| 120 | 336/0.67 | 15.3 | 5 | 26.1 | 39/0.67 | 13.8 | 1.4 | 40/0,20 | 0.8 | 8.3 | 80.2 | 9.95 | 3.866 |
| 150 | 427/0.67 | 17.1 | 5 | 27.9 | 48/0.67 | 17 | 1.4 | 40/0,20 | 0.8 | 8.6 | 84.6 | 11.5 | 4.822 |
| 185 | 518/0.67 | 19.2 | 5 | 30 | 63/0.67 | 22.3 | 1.4 | 40/0,20 | 0.8 | 9 | 90 | 13.3 | 5.983 |
| 240 | 672/0.67 | 21.8 | 5 | 32.6 | 77/0.67 | 27.2 | 1.4 | 40/0,20 | 0.8 | 9.6 | 96.8 | 16 | 7.708 |
| 300 | 854/0.67 | 24.4 | 5 | 35.2 | 98/0.67 | 34.6 | 1.4 | 40/0,20 | 0.8 | 10.2 | 103.6 | 19 | 9.649 |
| Type | 241.11 | 11/11kV | |||||||||||
| 25 | 209/0.40 | 7.2 | 7.6 | 23.4 | 63/0.30 | 4.5 | 1.8 | 24/0,20 | 0.8 | 7.8 | 73.2 | 6.55 | 862 |
| 35 | 285/0.40 | 8.5 | 7.6 | 24.7 | 87/0.30 | 6.2 | 1.8 | 24/0,20 | 0.8 | 8.1 | 76.6 | 7.35 | 1.199 |
| 50 | 380/0.40 | 10 | 7.6 | 26.2 | 114/0.30 | 8.1 | 1.8 | 40/0,20 | 0.8 | 8.5 | 80.6 | 8.3 | 1.686 |
| 70 | 203/0.67 | 12 | 7.6 | 28.2 | 36/0.67 | 12.7 | 1.8 | 40/0,20 | 0.8 | 8.9 | 85.7 | 9.85 | 2.394 |
| 95 | 259/0.67 | 13.2 | 7.6 | 29.4 | 36/0.67 | 12.7 | 1.8 | 40/0,20 | 0.8 | 9.3 | 89.1 | 11 | 3.114 |
| 120 | 336/0.67 | 15.3 | 7.6 | 31.5 | 39/0.67 | 13.8 | 1.8 | 40/0,20 | 0.8 | 9.7 | 94.4 | 12.7 | 3.866 |
| 150 | 427/0.67 | 17.1 | 7.6 | 33.3 | 48/0.67 | 17 | 1.8 | 40/0,20 | 0.8 | 10 | 98.9 | 14.4 | 4.822 |
| 185 | 518/0.67 | 19.2 | 7.6 | 35.4 | 63/0.67 | 22.3 | 1.8 | 40/0,20 | 0.8 | 10.4 | 104.2 | 16.3 | 5.983 |
Tell us your quantity and requirements — we reply within one business day.
Mining CablesGeneral use cable for mines (except for underground coal mines). Suitable to trailing and reeling due to its’ smaller dimensions.
Mining CablesGeneral use cable for mines (except for underground coal mines). It has smaller dimensions but strong structure.
Mining CablesGeneral use cable for mines (except for underground coal mines)
Share your specifications and quantities. Our team will review your request and come back with sourcing options and a quotation.