BS 6708 Type 730 Mining Cable

Used as trailing cable for supplying large machines.

Rated voltage3800/6600 V
ConductorElectrolytic, stranded, tinned copper wire IEC 60228 Class 5
InsulationEPR
Outer sheathHeavy duty chloroprene outer sheath.
  • Quoted to your quantity
  • Documentation on request
  • International delivery

Product Overview

Used as trailing cable for supplying large machines.

Technical Specifications

Rated voltage3800/6600 V
ConductorElectrolytic, stranded, tinned copper wire IEC 60228 Class 5
InsulationEPR
Outer sheathHeavy duty chloroprene outer sheath.
ScreenTinned copper / Nylon braided screen over phase cores.
LayupAll cores are laid up around the bare copper earth core and in contact with each other.
BeddingRubber based bedding compound.
Related standardsBS 6708
Test voltage15 kV
Cross Section3×353×503×703×953×120+163×150+16
Phase Conductors
Number and cross sectionmm23×353×503×703×953×1203×150
Insulation thicknessmm5.05.05.05.05.05.0
Earth Conductor
Number and cross sectionmm2––––1×161×16
Strandingmm––––126/0,40126/0,40
Conductor diameterNom. mm––––5.505.50
Insulation thicknessmm––––barebare
Cable details
Outer sheath thicknessmm6.06.36.87.37.68.0
Min. overall diametermm57.562.067.573.176.982.1
Max. overall diametermm60.565.071.476.980.986.0
Min. bending radiusmm605650714769809860
Appx. cable weightkg/km4.85.97.18.59.9511.4
Copper weightkg/km1.31.82.53.254.25
Electrical details
“Continuous current rating at 25°C Ambient”A135170205250295320
Max. DC resistance at 20°C
Phase conductorsΩ /km0.5650.3930.2770.2100.1640.132
3 screens and earth (if applied) in parallel connectionΩ /km0.810.780.550.420.320.26