BS 6708 Type 44 Mining Cable

Used for supplying hand-held driling machines.

Rated voltage125/72 V
ConductorElectrolytic, stranded, tinned copper wire IEC 60228 Class 5
InsulationEPR
Outer sheathHeavy duty chloroprene outer sheath.
  • Quoted to your quantity
  • Documentation on request
  • International delivery

Product Overview

Used for supplying hand-held driling machines.

Technical Specifications

Rated voltage125/72 V
ConductorElectrolytic, stranded, tinned copper wire IEC 60228 Class 5
InsulationEPR
Outer sheathHeavy duty chloroprene outer sheath.
SeparatorColored Textile tape for core identification.
ScreenTinned copper / Nylon braided screen over phase cores. Pilot core and ground core are not screened.
LayupAll cores are laid up in contact with each other.
BeddingRubber based bedding compound.
Related standardsBS 6708
Test voltage1,5 kV
Cross Section5×6
Phase Conductor
Number and cross sectionmm23×6
Insulation thicknessmm1.00
Total screen cross sectionmm211
Earth Conductor
Number and cross sectionmm21×6
Strandingmm84/0,30
Conductor diameterNom. mm3.30
Insulation thicknessmm1.00
Pilot Conductor
Number and cross sectionmm21×6
Strandingmm84/0,30
Conductor diameterNom. mm3.30
Insulation thicknessmm1.00
Cable details
Min. overall diametermm24.7
Max. overall diametermm26.7
Min. bending radiusmm241
Radial diameter of outer sheathmm3.0
Max. pulling tensionkgf218
Appx. cable weightkg/km1.15
Copper weightkg/km400
Electrical details
“Continuous current rating at 25°C Ambient”A46
Short curc›it current for 1 sA908
Max. DC resistance at 20°C
Phase and earth conductorsΩ /km11
Pilot ConductorΩ /km11
3 screens in parallel connectionΩ /km3.48