Mining CablesCables
AS/NZS 2802 Type 455 Mining Cable
General use cable for mines (except for underground coal mines). Suitable to trailing and reeling due to its’ smaller dimensions.
3.3/3.3 kV, 6.6/6.6 kV, 11/11 kV, 22/22 kV

Used for supplying excavating, crushing machines and equipment.
Used for supplying excavating, crushing machines and equipment.
| Rated voltage | 1900/3300 V |
|---|---|
| Conductor | Electrolytic, stranded, tinned copper wire IEC 60228 Class 5 |
| Insulation | EPR (Ground core is not insulated in T‹P 320) |
| Outer sheath | Heavy duty chloroprene outer sheath. |
| Separator | Semiconduct ing layer |
| Separator | Semiconducting layer |
| Screen | Tinned copper / Nylon braided screen over insulated cores. |
| Layup | All cores are laid up in contact with each other. |
| Bedding | Rubber based bedding compound. |
| Armour | Galvanized steel pliable armour. |
| Separator | Galvanized steel tape or water blocking tape (optional) |
| Related standards | MGM 111/1985 |
| Test voltage | 7,5 kV |
| Cross Section | 3×16+16 | 3×25+16 | 3×35+16 | 3×50+25 | 3×70+35 | 3×95+50 | 3×120+70 | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| MGM 111 TYPE 320 | |||||||||||||||
| Phase Conductor | |||||||||||||||
| Insulation thickness | mm | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | |||||||
| Earth Conductor | |||||||||||||||
| Number and cross section | mm2 | 1×16 | 1×16 | 1×16 | 1×25 | 1×35 | 1×50 | 1×70 | |||||||
| Stranding | mm | 126/0,40 | 126/0,40 | 126/0,40 | 196/0,40 | 276/0,40 | 396/0,40 | 360/0,50 | |||||||
| Insulation thickness | mm | – | – | – | – | – | – | – | |||||||
| Cable details | |||||||||||||||
| Radial thickness of inner sheath | mm | 2.5 | 2.5 | 3.5 | 3.8 | 3.8 | 5.0 | 5.0 | |||||||
| Size of armour | mm | 7/0,7 | 7/0,7 | 7/0,9 | 7/0,9 | 7/0,9 | 7/1,25 | 7/1,25 | |||||||
| Radial thickness of outer sheath | mm | 4.0 | 5.0 | 5.3 | 5.8 | 6.7 | 6.8 | 7.2 | |||||||
| Min. overall diameter | mm | 51.5 | 56.7 | 60.7 | 68.6 | 74.7 | 85.3 | 88.5 | |||||||
| Max. overall diameter | mm | 55.8 | 60.1 | 64.1 | 72.3 | 78.4 | 89.2 | 93.7 | |||||||
| Min. bending radius | mm | 503 | 541 | 577 | 651 | 706 | 803 | 844 | |||||||
| Appx. cable weight | kg/km | 4.7 | 6.15 | 7.3 | 9.1 | 11 | 11.8 | 16.7 | |||||||
| Copper weight | kg/km | 990 | 1.3 | 1.65 | 2.25 | 3.15 | 4.2 | 5.05 | |||||||
| Electrical details | |||||||||||||||
| “Continuous current rating at 25°C Ambient” | A | 85 | 110 | 135 | 170 | 205 | 250 | 295 | |||||||
| Max. DC resistance at 20°C | |||||||||||||||
| Phase Conductor | Ω /km | 1.24 | 0.795 | 0.565 | 0.393 | 0.277 | 0.21 | 0.164 | |||||||
| 3 screens and earth in parallel connection | Ω /km | 0.70 | 0.60 | 0.50 | 0.50 | 0.34 | 0.28 | 0.18 | |||||||
| Armour | Ω /km | 1.40 | 0.96 | 0.90 | 0.79 | 0.73 | 0.47 | 0.44 | |||||||
| Cross section | 4×16 | 4×25 | 4×35 | 4×50 | 4×70 | 4×95 | 4×120 | 4×150 | |||||||
| MGM 111 TYPE 321 | |||||||||||||||
| Conductors | |||||||||||||||
| Number and cross section | mm2 | 4×16 | 4×25 | 4×35 | 4×50 | 4×70 | 4×95 | 4×120 | 4×150 | ||||||
| Stranding | mm | 126/0,40 | 196/0,40 | 276/0,40 | 396/0,40 | 360/0,50 | 475/0,50 | 608/0,50 | 756/0,50 | ||||||
| Insulation thickness | mm | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | ||||||
| Cable details | |||||||||||||||
| Radial thickness of inner sheath | mm | 2.5 | 2.5 | 3.5 | 3.8 | 3.8 | 5.0 | 5.0 | 5.0 | ||||||
| Size of armour | mm | 7/0,7 | 7/0,7 | 7/0,9 | 7/0,9 | 7/0,9 | 7/1,25 | 7/1,25 | 7/1,25 | ||||||
| Radial thickness of outer sheath | mm | 4.0 | 5.0 | 5.3 | 5.8 | 6.7 | 6.8 | 7.2 | 7.6 | ||||||
| Min. overall diameter | mm | 51.5 | 56.7 | 60.7 | 68.6 | 74.7 | 85.3 | 88.5 | 95.4 | ||||||
| Max. overall diameter | mm | 55.8 | 60.1 | 64.1 | 72.3 | 78.4 | 89.2 | 93.7 | 99.3 | ||||||
| Min. bending radius | mm | 503 | 541 | 577 | 651 | 706 | 803 | 844 | 894 | ||||||
| Appx. cable weight | kg/km | 4.85 | 6.4 | 7.65 | 9.5 | 11.55 | 12.5 | 17.45 | 19 | ||||||
| Copper weight | kg/km | 1.1 | 1.5 | 2 | 2.65 | 3.7 | 4.9 | 5.8 | 6.85 | ||||||
| Electrical details | |||||||||||||||
| “Continuous current rating at 25°C Ambient” | A | 85 | 110 | 135 | 170 | 205 | 250 | 295 | 345 | ||||||
| Max. DC resistance at 20°C | |||||||||||||||
| Conductors | Ω /km | 1.24 | 0.795 | 0.565 | 0.393 | 0.277 | 0.21 | 0.164 | 0.124 | ||||||
| Armour | Ω /km | 1.40 | 0.96 | 0.90 | 0.79 | 0.73 | 0.47 | 0.44 | 0.38 |
Tell us your quantity and requirements — we reply within one business day.
Mining CablesGeneral use cable for mines (except for underground coal mines). Suitable to trailing and reeling due to its’ smaller dimensions.
Mining CablesGeneral use cable for mines (except for underground coal mines). It has smaller dimensions but strong structure.
Mining CablesGeneral use cable for mines (except for underground coal mines)
Share your specifications and quantities. Our team will review your request and come back with sourcing options and a quotation.