HVAC Air-Conditioning Circulation Pump

Low-noise HVAC chilled-water pump to EN 733 / ISO 9908: 9–1080 m³/h, 13–56 m, -10 to +104 °C, ductile iron casing, bronze wear rings. For air conditioning.

StandardBS EN 733, ISO 9908
Flow9–1080 m³/h
Head13–56 m
Liquid temperature-10 to +104 °C
  • Quoted to your quantity
  • Documentation on request
  • International delivery

Product Overview

A single-stage end-suction pump developed specifically for air-conditioning chilled-water and condenser-water circuits. A dedicated low-speed, low-noise motor keeps the plant room quiet, and the pump meets the efficiency requirements of modern HVAC designs.

Quiet and leak-free

The low-noise HVAC motor gives smooth running, and the mechanical seal is rated for more than 10,000 hours in normal service, leak-free under high system pressure. Flush ports on the pump cover clean the seal chamber and cool the seal faces.

Back pull-out and few spare parts

Pump cover and impeller come out without disturbing the pipework. Only four shaft, bearing-bracket and coupling sizes are used across the range, which simplifies maintenance in large buildings with many pumps.

Materials

Ductile iron casing, cast iron impeller, bronze wear rings, stainless steel shaft and quality bearings as standard; 316 stainless casing and stainless or copper-alloy impellers on request.

Frequently asked questions

Is it suitable for glycol mixtures?

Yes, for water and liquids with similar properties, including usual glycol mixtures – tell us the concentration for the selection.

What noise level can I expect?

The pump uses a dedicated low-speed HVAC motor; we provide noise data with the quotation.

What information do you need for a quotation?

Flow rate, head or vacuum level, the liquid or gas and its temperature, required materials, motor voltage and frequency, and any standard or ATEX zone. A data sheet or the nameplate of an existing pump is ideal.

Need a quotation for the HVAC Air-Conditioning Circulation Pump? Send us your requirements and the delivery address – we reply with a technical proposal, price and lead time. Request a quote.

Technical Specifications

StandardBS EN 733, ISO 9908
Flow9–1080 m³/h
Head13–56 m
Liquid temperature-10 to +104 °C
MaterialsDuctile iron casing, cast iron impeller, bronze wear rings, stainless shaft
Seal lifemechanical seal, > 10,000 h normal life

Applications

  • Chilled-water circuits
  • Condenser-water circuits
  • District cooling
  • Hotels, hospitals, offices and malls
  • Data-centre cooling loops

Features

  • Designed for chilled and condenser water
  • Low-speed, low-noise motor
  • Seal life > 10,000 h, flush ports
  • Back pull-out design
  • Interchangeable with EN 733 pumps

Request Information About This Product

Tell us your quantity and requirements — we reply within one business day.

Related Products

Have a product requirement?

Share your specifications and quantities. Our team will review your request and come back with sourcing options and a quotation.