Product Overview
Detecting Gas
Open Path Gas Detection System | Continuous Monitoring for Combustible Hydrocarbon Gases
The SafEye Xenon 700, manufactured by Crowcon, is an open path fixed gas detection system. This gas detector integrates well-proven and superior Xenon Flash technology which has an excellent operational record in many installations ranging from the deserts of Africa and Asia and the very hot and humid Far East, to the wet and cold North Sea and the dry and cold regions of Alaska.
The Crowcon SafEye 700 Optical Open Path (Line-of-Sight) Gas Detection System employs “spectral fingerprint” analysis of the atmosphere using the Differential Optical Absorption Spectroscopy (DOAS) technique in a unique (patented) method. Using superior “Xenon Flash” technology the SafEye range is immune to false alarms caused by partial blockage and extreme weather conditions (fog, rain or snow) and direct or reflected sunlight, flame or other black body radiation sources.
Detecting Gas in Hazardous Areas
Features
- Reliable detection of gas leaks including a wide range of gaseous hydrocarbons, such as: Alkanes, Alkenes (C1-C8), Alcohols, LNG, LPG, Ethylene, etc.
- One person can simply and easily align and commission SafEye with separate horizontal and vertical adjustments.
- Direct reading, high sensitivity and fast response (3 sec) ensures instant action and maximum safety.
- Provides relatively wide angle of view, better than 1˚, to withstand vibration, mechanical shock and displacements.
- Rugged Structure – Stainless steel 316L, IP66/67, Zone 1 ready design.
- Electro-optical system, not affected by chemicals
- Standard 4-20 mA output with a new mode (3 mA) “Maintenance call” or RS-485, Modbus compatible output to allow networking (up to 256 detectors) to a central monitoring / PC system. This feature also enables easy maintenance, local and remote diagnostic tools.
- Less units needed for protection compared with point type detection. One system can replace from 5 to 20 point gas detectors. Low cost of ownership, much lower installation cost!
- Thousands of first generation Flash Type SafEye are installed on offshore platforms, FPSO’s, refineries, and other onshore applications operated by British Petroleum (BP), Shell, ExxonMobil, Statoil, and others.
- Well-proven in harsh environments (rain, snow, fog, hot and humid weather), up to 90% beam blockage, an excellent operational record in many installations worldwide.
– Heated Optics on the source and detector increase the temperature of the optical surface to reduce icing, condensation and snow.
– Resilient and excellent performance withstanding extreme vibrations, displacement and shock.
– Solar blind and immune to false alarms from industrial environments
Not all gas clouds are hazardous
Only if a flammable gas cloud or plume is wide enough to allow flame acceleration to speeds greater than 100 m/sec does it become a significant threat.
- Just as an athlete performing the long jump needs a run-up distance, so too a flame front needs distance to reach the velocities which cause the damaging effects of over-pressure, pressure pulse and windage.
- The generally accepted quantity of gas that creates the potential to cause consequential damage if ignited is a cloud of the size 5 m diameter a stoichiometric concentration (about 200% LEL).
- To provide a safety margin, this concentration is halved to 100% LEL. Thus an open path beam traversing this cloud would indicate 5 LEL.m.
- Location of the SafEye 700 Open-Path Gas Detector is less important than with point type detectors as it provides a warning alarm from a diluted gas cloud and does not need to be close to the leakage source.
- Point type detectors measure gas at their location in terms of % LEL, whereas open-path gas detectors measure the amount of gas anywhere along the length of the path, in terms of the integral of concentration and length (LEL x meters).
Specification
Crowcon SafEye 700 consists of an advanced Xenon Flash infrared transmitter (source) and an infrared detector (receiver), separated over a line of sight from 13 ft. (4 m) up to 460 ft. (140 m) to detect flammable gas presence, even when challenged by extremely harsh environments where dust, fog, rain, snow or vibration can cause a high reduction of signal.
The SafEye Xenon 700 analyses atmospheric absorption at three selected spectral bands, two in a region where the target gas absorbs and one where it does not absorb. The ratio between these absorption lines can provide accurate information of the gas concentration along an optical path. The reference sensor detects beam blockage, compensates for changing humidity and detects failed light source or dirty optics.
Crowcon Safeye’s source and detector units are both housed in low profile, rugged, stainless steel, ATEX approved enclosures.
The main enclosure is EEx d flameproof with an integral, segregated, EEx e increased safety terminal section.
The hand-held communication unit can be connected in-situ via the intrinsically safe approved (EEx ia) data port on the detector. SafEye 700 includes heated optics on the transmitter (source) and receiver (detector) to address icing, condensation and snow.
Electrical Specifications
- Power Supply: 24VDC nominal (18-32 VDC)
- Power Consumption (peak includes heated optics): Detector: 150mA (300mA Peak) | Source: 100mA (300mA Peak)
- Electrical Connection (specify): 2 x 3/4″ – 14NPT conduits or 2 x M25 x 1.5mm ISO
- Electrical Input Protection: per MIL-STD-1275B
- Electromagnetic Compatibility: EMI/RFI protected CE Marked
General Specifications
Mechanical Specifications
Hazardous Area Equipment
Visit hazardous area gas detectors for explosion and flameproof gas monitoring and detection instruments with certification for potentially explosive atmospheres, including Zone 1 and Zone 2 (according to ATEX and IECEx) and Class/Division categories (according to North American standards).
:arrow: Did you know? Crowcon fixed gas detectors protect plant; portable gas detectors protect people.
Flame, Heat, Gas Detectors & Detection Systems
Hazardous area industries including offshore oil/gas platforms and FPSOs, onshore oil refineries, processing plants, pipelines, storage farms and LPG/LNG plants all utilise or produce a wide range of hazardous flammable liquids and gases that can be detected using correctly specified flame and gas detectors.
Detecting toxic and flammable gases requires the detectors to be classified and certified according to the specific IECEx or ATEX standard – we distribute flame and fire detectors manufactured by Spectrex to operate in the harshest environmental conditions including self-contained stand-alone devices designed for direct connection to control and alarm systems or automatic fire extinguishing systems.
Our range of Hazardous Area Fire & Gas Detection System products also includes Explosion Proof Warning Systems & Hazardous Area Lighting – comprehensive range of intrinsically safe, flameproof and explosion proof alarm sounders, sirens, bells and horns, loudspeakers and beacons.
♦ LV Power Products | Junction Boxes & Enclosures ATEX | Plugs ATEX | Control Stations ATEX | Isolators ATEX