Chromalox HSRL 8-2CT 8W/FT 240V Trace Heating Cables

Chromalox HSRL 8-2CT hazardous area trace heating cables are self regulating and provide process temperature maintenance and frost protection to pipework, instrument lines, tanks and drums up to 65º Celsius – with…

CategoryHeat Tracing Cables & Systems
  • Quoted to your quantity
  • Documentation on request
  • International delivery

Product Overview

Trace Heating Cables

Chromalox HSRL 8-2CT hazardous area trace heating cables are self regulating and provide process temperature maintenance and frost protection to pipework, instrument lines, tanks and drums up to 65º Celsius – with CSA and FM certification Chromalox HSRL heat trace cables ensures operating integrity in Div. 1 hazardous areas.

  • Manufacturer: Chromalox
  • Heating Cable Range: HSRL
  • Heating Cable Code: HSRL 8-2CT
  • Maximum Maintain Temperature : 65° Celsius
  • Maximum Continuous Exposure Temperature : Power Off 85° Celsius
  • Cable Type: Self Regulating, Energy Efficient Trace Heating Cables
  • Cable Ratings: 8 Watts Per Foot @ 50°F
  • Cable Voltage: 240V
  • Maximum Heating Cable Circuit Length: Up to 420 feet
  • Minimum Cable Bend Radius : 1-1/8″
  • Weight/1000′: 66 lbs
  • See Also: Trace Heating

Construction

  1. Twin 16 AWG Copper Buss Wires are able to Provide reliable electrical current capability.
  2. Semiconductive Polymer Core Matrix is the ‘self regulating component of the cable and it’s electrical resistance varies with temperature.
  3. Polyolefin Jacket is flame retardant and electrically insulates the matric and buss wires and provides resistance to water and some inorganic chemical solutions.
  4. Tinned Copper Braid that provides additional mechanical protection in any environment, and a positive ground path.
  5. High Temperature Fluoropolymer Overjacket is a corrosion resistant, flame retardant overjacket is highly effective in many environments.

Maximum Circuit Lengths in Feet

Hazardous Area Approvals

FM Approvals

  • Class I, Division 1, Groups B, C, D
  • Class II, Division 1, Groups E, F, G
  • Class III, Division 1
  • 3 Watt rated T6 temperature class
  • 5 and 8 Watt rated T5 temperature class
  • 10 Watt rated T4A temperature class

CSA

  • Class I, Division 1, Groups B, C, D
  • Class II, Division 1, Groups E, F, G
  • 3 Watt rated T6 temperature class
  • 5 and 8 Watt rated T5 temperature class
  • 10 Watt rated T4A temperature class

Technical Specifications

CategoryHeat Tracing Cables & Systems
Maximum Cable Circuit Length (Ft.) by Start-Up Temperature (°F) and Breaker Size (Amps)
Heating Cable RatingHSRL 8-2CT Trace Heating
50°F Start-Up (Ft.) Circuit Breaker10 A185
15 A285
20 A375
25 A420
30 ANR
40 ANR
0°F Start-Up (Ft.) Circuit Breaker10 A135
15 A200
20 A265
25 A335
30 A385
40 A420
-20°F Start-Up (Ft.) Circuit Breaker10 A120
15 A175
20 A235
25 A300
30 A350
40 A420