6.6kV Terminal – HV High Voltage Cable Terminal Zone 1 Hazardous Area ATEX

Abtech MV Terminal is a component suitable for use with high voltage hazardous area electrical enclosures and junction boxes provide safe power distribution for 4.4kV to 6.6kV systems up to 240sqmm cables…

CategoryOther Hazardous Area & Process Products
  • Quoted to your quantity
  • Documentation on request
  • International delivery

Product Overview

Abtech MV Terminal is a component suitable for use with high voltage hazardous area electrical enclosures and junction boxes provide safe power distribution for 4.4kV to 6.6kV systems up to 240sqmm cables – ATEX certified for Zone 1 of MV cables in hazardous area locations.

Abtech MV Terminal (6.6kV) is available in three, four and six way configurations: the terminals are both ATEX and IECEx approved and is rated for a maximum current of 250A.

Abtech MV Terminals can be specified to be linked in pairs or multiples and are suitable for high ambient temperature applications and are compatible for use with Abtech SX stainless steel enclosures.

Operating Temperature Rating

  • Standard: -40°C to +130°C

High Voltage HV ENCLOSURE Specification

  • Product Type: Medium Voltage Terminal
  • Material Plastic: UTR Laminate GP03 grade 1494
  • Operating Temp Rating: -40°C to +130°C
  • Crimp Lugs: M8 single hole, sizes 6mm2 up to 240mm2
  • Mounting: 4 x M8 clearance holes
  • Certification Area: Classification Zone 1 & 21, Gas and Dust
  • Type of Protection: Ex e (Increased Safety)
  • Apparatus Coding: Ex e IIC Gb
  • Certificate Number: ATEX: CML 15ATEX3096U / IECEx: CML 15.0051U

Enclosure Options

  • Abtech Lxx Linking: 1st x = link type (pairs, triple) 2nd x = Quantity of links required

Add the required suffix to the product reference. Example: TATEMV6TL23 – 6 way 6.6kV max terminal block linked in pairs, three links.

Technical Specifications

CategoryOther Hazardous Area & Process Products
Abtech Part RefWidth (mm) DimensionHeight (mm) Dimension YDepth (mm) Dimension ZMaximum Voltage (kV) *Maximum Current (A)Maximum Conductor Size (mm²)Maximum WaysWeight (kg)Hazardous Area Enclosure
XX(M)YY(M)
TATEMV31681532202001024.4kV250240sqmm31.8Zone 1
TATEMV42121972202001024.4kV250240sqmm42.4Zone 1
TATEMV63002852202001024.4kV250240sqmm63.7Zone 1
TATEMV3T1681532202001146.6kV250240sqmm31.8Zone 1
TATEMV4T2121972202001146.6kV250240sqmm42.4Zone 1
TATEMV6T3002852202001146.6kV250240sqmm63.7Zone 1

Request Information About This Product

Tell us your quantity and requirements — we reply within one business day.

Related Products

Have a product requirement?

Share your specifications and quantities. Our team will review your request and come back with sourcing options and a quotation.