BS 6708 Type 11 Mining Cable

Used for supplying excavating, crushing machines and equipment.

Rated voltage640/1100 V
ConductorElectrolytic, stranded, tinned copper wire IEC 60228 Class 5
InsulationEPR
Outer sheathHeavy duty chloroprene outer sheath.
  • Quoted to your quantity
  • Documentation on request
  • International delivery

Product Overview

Used for supplying excavating, crushing machines and equipment.

Technical Specifications

Rated voltage640/1100 V
ConductorElectrolytic, stranded, tinned copper wire IEC 60228 Class 5
InsulationEPR
Outer sheathHeavy duty chloroprene outer sheath.
SeparatorColored Textile tape for core identification.
ScreenTinned copper / Nylon braided screen over phase and pilot cores
LayupAll cores are laid up in contact with each other.
BeddingRubber based bedding compound.
Related standardsBS 6708
Test voltage3 kV
Cross Section3×16+16
Phase Conductor
Number and cross sectionmm23×16
Insulation diameterNom. mm8.60
Screen diameterNom. mm10.90
Pilot Conductor
Number and cross sectionmm21×16
Strandingmm126/0,40
Conductor diameterNom. mm5.50
Insulation diameterNom. mm8.60
Screen diameterNom. mm10.90
Cable details
Min. overall diametermm30.9
Max. overall diametermm33.0
Min. bending radiusmm264
Max. pulling tensionkgf384
Appx. cable weightkg/km2
Copper weightkg/km1.1
Electrical details
“Continuous current rating at 25°C Ambient”A85
“Intermittent current rating at 25°C Ambient”A96
Max. DC resistance at 20°C
Phase ConductorΩ /km1.24
Pilot ConductorΩ /km1.24
3 screens and earth in parallel connectionΩ /km1.05
Nom. reactance at 50HzΩ /km0.109
Nom. reactance at 60HzΩ /km0.131
Min. insulation resistance at 20°CM Ω /km435
3 phase voltage drop on full load currentmV/A/m2.62

Request Information About This Product

Tell us your quantity and requirements — we reply within one business day.

Related Products

Have a product requirement?

Share your specifications and quantities. Our team will review your request and come back with sourcing options and a quotation.