Chromalox CWM 8-1C 8W/FT 120V Trace Heating Cables

CWM trace heating cables manufactured by Chromalox, including CWM 8-1C provide frost protection to pipework and valves, tanks and associated mechanical services – suitable for hazardous area zones including Div 2. For…

CategoryHeat Tracing Cables & Systems
  • Quoted to your quantity
  • Documentation on request
  • International delivery

Product Overview

Trace Heating Cables

  • Manufacturer: Chromalox
  • Heating Cable Range: CWM
  • Heating Cable Code: CWM 8-1C 8W/FT 120V
  • Cable Type: Constant Wattage, Medium Temperature
  • Circuit Load: 0.067 Amps/Ft.
  • Cable Voltage: 120V
  • Output Wattage at 120V: 8 W/Ft.
  • Maximum Heating Cable Circuit Length: 290 Ft.
  • Length Between Nodes: 36″
  • Approximate Cable Size: 0.30″W x 0.25″H
  • Minimum Cable Bend Radius: 1-1/4″
  • Heating Cable Maximum Exposure Temperature: Power Off, 392°F (200°C)
  • See Also: Trace Heating

CWM trace heating cables manufactured by Chromalox, including CWM 8-1C provide frost protection to pipework and valves, tanks and associated mechanical services – suitable for hazardous area zones including Div 2. For use on metallic pipes only.

Heating Cable Applications

  • Process Pipework Maintenance
  • Frost Protection of Pipework
  • Fluid Flow, Transfer & Viscosity Maintenance

Cable Ordering Information

  1. Twin 12 AWG Copper Buss Wires – Provide reliable, consistent electrical current
  2. FEP Insulation Jacket – Electrically insulates buss wires
  3. Pairing Jacket – Secures two buss wires together and provides wrapping surface for Nichrome wire
  4. Nickel Chromium Wire – Cable heating component
  5. FEP Insulation – Rugged outer sheath protects heating cable, assures longer service life, and provides protection against environmental application hazards
  6. Tinned Copper Braid – Plated copper braid increases robust construction, provides ground path and provides additional protection in any location (suffix “C” in model number)
  7. FEP – Fluoropolymer overjacket, over the braid, provides protection from most aqueous and chemically corrosive solutions (suffix “T” in model number) – ideal for trace heating systems installed in hazardous areas with explosive atmospheres

Hazardous Area Approvals

UL Listed for ordinary areas.

CSA Certified for ordinary and:

  • Class I, Div. 2, Groups A, B, C, D
  • Class II, Div. 2, Groups F, G. Rated T3 Temperature Class (Exception: Cable surface temperature shall not exceed 190°C in Class II, Div. 2, Group F; 165°C in Class II, Div. 2, Group G)

Technical Specifications

CategoryHeat Tracing Cables & Systems
Output (W/Ft.)Nominal Voltage (Vac)ModelDescriptionWt./1000′ (Lbs.)Chromalox Order Code
8120CWM 8-1CStandard tinned-copper metallic braid for additional protection and ground path96392139
CWM 8-1CTFluoropolymer corrosion resistant overjacket over braid for hostile or corrosive environments110392163