Crowcon Gasmaster Gas Detection Control Panel

Manufactured by Crowcon, Gasmaster is a compact, versatile and powerful control panel for gas detection which combines simple operation with an extensive array of input and output functions.

CategoryGas Detection
  • Quoted to your quantity
  • Documentation on request
  • International delivery

Product Overview

Crowcon Gasmaster

Manufactured by Crowcon, Gasmaster is a compact, versatile and powerful control panel for gas detection which combines simple operation with an extensive array of input and output functions.

The Crowcon Gasmaster provides all the information you need about your gas and fire detectors at a glance. The large multi-lingual display shows gas levels from all detectors simultaneously and enables system adjustment and testing using buttons on the front panel.

Crowcon Gasmaster can operate ‘stand-alone’ or interface with any alarm devices and control systems using a selection of outputs.

Detection Control Panel Features

External Features:

  • All gas levels are displayed simultaneously – enables full systems status check at a glance
  • Alarm messages can be customised to indicate the name or location of any detector in alarm
  • The LCD can be set to display in many languages
  • Menu system is intuitive and easy to use – enables configuration changes to be made easily
  • All functions, from day-to-day operation to re-calibration, can be carried out from the front panel – routine testing can be performed rapidly
  • Event log feature – enables system fault and alarm history to be viewed
  • Provides analogue, relay and Modbus outputs – facilitating communication around the site
  • Flexibility – Gasmaster can monitor up to four detectors in virtually any combination of gas detectors, fire zones or Environmental Sampling Unit*. Software enables re-configuration and event log upload in an instant**
  • Two levels of independent alarm per channel – can be configured to suit site requirements
  • Remote inhibit and re-set facilities – enables control from any point on your site
  • Compatible with a 4-20mA or mV pellistor-type gas detector – mV pellistor detectors reduce system purchase and maintenance costs
  • You only need to purchase the required number of input modules – 1,2 and 3-channel systems can be extended later by adding additional modules***

* Contact our team for details

** Event Log access requires optional PC communications kit

*** Gasmaster 4 only

Specfication

Visit hazardous area gas detectors for explosion and flameproof gas monitoring and detection instruments with certification for potentially explosive atmospheres, including Zone 1 and Zone 2 (according to ATEX and IECEx) and Class/Division categories (according to North American standards).

Technical Specifications

CategoryGas Detection
Crowcon Order CodeGasmaster 1Gasmaster 4
Size288 x 278 x 110mm (11.3 x 10.9 x 4.3 ins)
Weight4.5kg (10lbs)
Enclosure materialBack-box: cast aluminium Front cover: ABS (flame retardant)
Ingress protectionIP65
Power100-240Vac 50-60Hz or 20-30Vdc, 60W max
Battery back-up1.2Ah batteries fitted internally
Operating temperature-10°C to + 50ºC (14°F to 122°F)
Humidity0 to 95% RH non-condensing
InputsGasOne 2 or 3 wire 4-20mA gas detector (sink or source) or mV pellistor flammable gas detectorOne to four 2 or 3 wire 4-20mA gas detectors (sink or source) or mV pellistor flammable gas detectors
FireOne loop of up to 20 conventional smoke/heat detectors or manual call points, or one flame detector (4-20mA or digital contact signal)One to four loops of up to 20 conventional smoke/heat detectors or manual call points, or one to four flame detectors
Environmental Sampling UnitFor use with one Crowcon ESU fanFor use with one to four Crowcon ESU fans
Remote inhibitVia normally open contact
Remote resetVia normally open contact
OutputsRelays DPCO contacts rated 250Vac 8A. Relays can be set as energised or de-energised, latching or non-latching, latching acceptableLow alarm. High alarm. Fault. Alarm relays can be set for rising or falling alarms. Hysteresis can be adjusted on low alarmsLow alarm and high alarm per channel plus common low, high and fault. Alarm relays can be set for rising or falling alarms. Hysteresis can be adjusted on low alarms
A/V alarm drive12Vdc or 24Vdc 650mA max. drive. Suitable for +ve or -ve switched alarms
Analogue4-20mA (current source, max. loop resistance 700Ω) or 1-5Vdc (min. load 50kΩ )4-20mA for each channel (current source, max. loop resistance 700Ω) or 1-5Vdc (min. load 50kΩ)
Serial linkRS-485 Modbus RTU for monitoring and control via DCS/SCADA/PLC systems
Communications portOptional port for PC configuration and event log upload
Event logging*Time-stamped log of up to 300 alarms, fault or system intervention activities
Panel indicationLCD back-lit display shows gas level (in ppb, ppm, % volume or % LEL units), and scrolling alpha-numeric status indication. LED’s for Alarm, Fault, Power and Warning. Integral 85dB sounder (at 10cm)
ApprovalsEMC: EN50270, EN60945, FCC Part 15, ICES002 ATEX: EN60079-25:2010
Functional safetyValidated to IEC61508SIL2