Crowcon Control PanelsCrowcon Hydra 256 Gas Detection System
Manufactured by Crowcon, Hydra is a range of gas detection control panel systems which are designed to monitor toxic and/or flammable gas hazards, particularly in car park applications.

Manufactured by Crowcon, Gasmaster is a compact, versatile and powerful control panel for gas detection which combines simple operation with an extensive array of input and output functions.
Manufactured by Crowcon, Gasmaster is a compact, versatile and powerful control panel for gas detection which combines simple operation with an extensive array of input and output functions.
The Crowcon Gasmaster provides all the information you need about your gas and fire detectors at a glance. The large multi-lingual display shows gas levels from all detectors simultaneously and enables system adjustment and testing using buttons on the front panel.
Crowcon Gasmaster can operate ‘stand-alone’ or interface with any alarm devices and control systems using a selection of outputs.
External Features:
* Contact our team for details
** Event Log access requires optional PC communications kit
*** Gasmaster 4 only
Visit hazardous area gas detectors for explosion and flameproof gas monitoring and detection instruments with certification for potentially explosive atmospheres, including Zone 1 and Zone 2 (according to ATEX and IECEx) and Class/Division categories (according to North American standards).
| Category | Gas Detection |
|---|
| Crowcon Order Code | Gasmaster 1 | Gasmaster 4 | |
| Size | 288 x 278 x 110mm (11.3 x 10.9 x 4.3 ins) | ||
| Weight | 4.5kg (10lbs) | ||
| Enclosure material | Back-box: cast aluminium Front cover: ABS (flame retardant) | ||
| Ingress protection | IP65 | ||
| Power | 100-240Vac 50-60Hz or 20-30Vdc, 60W max | ||
| Battery back-up | 1.2Ah batteries fitted internally | ||
| Operating temperature | -10°C to + 50ºC (14°F to 122°F) | ||
| Humidity | 0 to 95% RH non-condensing | ||
| Inputs | Gas | One 2 or 3 wire 4-20mA gas detector (sink or source) or mV pellistor flammable gas detector | One to four 2 or 3 wire 4-20mA gas detectors (sink or source) or mV pellistor flammable gas detectors |
| Fire | One loop of up to 20 conventional smoke/heat detectors or manual call points, or one flame detector (4-20mA or digital contact signal) | One to four loops of up to 20 conventional smoke/heat detectors or manual call points, or one to four flame detectors | |
| Environmental Sampling Unit | For use with one Crowcon ESU fan | For use with one to four Crowcon ESU fans | |
| Remote inhibit | Via normally open contact | ||
| Remote reset | Via normally open contact | ||
| Outputs | Relays DPCO contacts rated 250Vac 8A. Relays can be set as energised or de-energised, latching or non-latching, latching acceptable | Low alarm. High alarm. Fault. Alarm relays can be set for rising or falling alarms. Hysteresis can be adjusted on low alarms | Low alarm and high alarm per channel plus common low, high and fault. Alarm relays can be set for rising or falling alarms. Hysteresis can be adjusted on low alarms |
| A/V alarm drive | 12Vdc or 24Vdc 650mA max. drive. Suitable for +ve or -ve switched alarms | ||
| Analogue | 4-20mA (current source, max. loop resistance 700Ω) or 1-5Vdc (min. load 50kΩ ) | 4-20mA for each channel (current source, max. loop resistance 700Ω) or 1-5Vdc (min. load 50kΩ) | |
| Serial link | RS-485 Modbus RTU for monitoring and control via DCS/SCADA/PLC systems | ||
| Communications port | Optional port for PC configuration and event log upload | ||
| Event logging* | Time-stamped log of up to 300 alarms, fault or system intervention activities | ||
| Panel indication | LCD back-lit display shows gas level (in ppb, ppm, % volume or % LEL units), and scrolling alpha-numeric status indication. LED’s for Alarm, Fault, Power and Warning. Integral 85dB sounder (at 10cm) | ||
| Approvals | EMC: EN50270, EN60945, FCC Part 15, ICES002 ATEX: EN60079-25:2010 | ||
| Functional safety | Validated to IEC61508SIL2 | ||
Tell us your quantity and requirements — we reply within one business day.
Crowcon Control PanelsManufactured by Crowcon, Hydra is a range of gas detection control panel systems which are designed to monitor toxic and/or flammable gas hazards, particularly in car park applications.
Crowcon Control PanelsManufactured by Crowcon, Gasmonitor Plus is a flexible 19″ rack-based control panel system. This microprocessor-controlled unit is used throughout the world, both onshore and offshore.
Crowcon Control PanelsThe Vortex FP and Vortex FP Compact, manufactured by Crowcon, are ATEX certified Ex d Flameproof control panels for use in Zone 1 or Zone 2 hazardous areas such as on offshore…
Share your specifications and quantities. Our team will review your request and come back with sourcing options and a quotation.