Hazardous Area IS Ultrasonic Sensor (ATEX IECEx UL) – Deeter RPS-409A-1S2

Deeter RPS-409A-IS2 is hazardous area ultrasonic sensor that can be used in hazardous gas or dust environments classified as Zone 0, 1, 2, 20, 21, or 22 for ATEX/IECEx, and Class I,…

BrandDeeter
CategoryProcess Instrumentation
  • Quoted to your quantity
  • Documentation on request
  • International delivery

Product Overview

Deeter RPS-409A-IS2 is hazardous area ultrasonic sensor that can be used in hazardous gas or dust environments classified as Zone 0, 1, 2, 20, 21, or 22 for ATEX/IECEx, and Class I, II, or III for UL/cUL when used with approved intrinsic safety barrier(s).

The Deeter RPS-409A-IS2 has built in temperature compensation to provide accurate readings throughout the entire operating temperature range.

The RPS-409A-IS2 is designed to take advantage of today’s PLC and computer analog input cards. The numerical values that are programmed into the PLC or computer will determine the zero and span.

Features

  • Intrinsically safe and UL Listed
  • ATEX, cUL, IECEx & ANZEx approvals
  • Wide sensing and temperature ranges
  • Analog voltage output
  • Sync/Tx input line
  • PPS enclosure
  • LED Indicator

Liquid Level Sensors & Float Switches – Deeter Products

See how Deeter Electronics Group manufacture liquid level sensors and control equipment for commercial, industrial and hazardous area sensing of liquids with ATEX, IECEx and CSA Certified sensors.

Technical Specifications

BrandDeeter
CategoryProcess Instrumentation
Hazardous Area IS Ultrasonic Sensor Approval & Application StandardsAustralia and New Zealand – ANZEx 13.3010X Ex ia I Ma, Ex ia IIC T4 Ga, Ex ia IIIC T101°C Da Canada and USA – UL/cUL File # E226209 CL I, GPS A,B,C,D; CL II, GPS E,F,G; and CL III Europe (CENELEC) – DEMKO 12 ATEX 1103028X Ex I M1 / II 1 GD IECEx – IECEx UL 12.0001X Ex ia I T4 Ma, Ex ia IIC T4 Ga, Ex ia IIIC T101°C Da
Power Input16 – 30VDC Reverse Polarity Protected (A minimum of 24VDC must be applied to the power barrier)
Input Current24mA maximum with 24VDC applied to the power barrier
Ambient Temperature-40 – 60°C or -40 – 140°F
Humidity0% – 95% Non-Condensing
HousingPolyphenylene Sulfide (PPS) Enclosure with PPS and PTFE sensing face
OutputAnalog Voltage Output 0-10V (Load 100k Ohms to infinity) Short Circuit Protected
Hazardous Area IS Ultrasonic Sensor Part NumberDescriptionSensor RangeTransducer FrequencyResponse TimeVolts Per Inch
Deeter RPS-409A-40-IS20 – 10 VDC Analog Output4″ to 40″175kHz85ms0.250
Deeter RPS-409A-80-IS20 – 10 VDC Analog Output6″ to 80″135kHz85ms0.125
Deeter RPS-409A-144-IS2*0 – 10 VDC Analog Output10″ to 144″70kHz175ms0.069
Deeter RPS-409A-216-IS2*0 – 10 VDC Analog Output12″ to 216″70kHz175ms0.046

Request Information About This Product

Tell us your quantity and requirements — we reply within one business day.

Related Products