ATEX Plugs, Sockets & ConnectorsMarechal 2514015 | Female Socket-Outlet
Product Code: 2514015

Marechal DXN37C plugs and sockets are compact and watertight with a current rating of 10A, 230V and are ATEX certified for Zone 1 & Zone 2 hazardous areas.
Marechal DXN37C plugs and sockets are compact and watertight with a current rating of 10A, 230V and are ATEX certified for Zone 1 & Zone 2 hazardous areas.
DXN37C plugs and sockets are automatically IP66/IP67 when connected and the socket outlet itself is also watertight when the lid is closed providing a waterproof power plug seal.
Marechal DXN37C plugs and sockets comply with:
Install the socket-outlet facing downwards, with the latches on the sides.
Wiring
Remove an adequate length of cable outer sheath according to the accessory used.
Ensure that the cable sheathing extends through the through the cord grip into the handle or box as required to achieve the intended sealing and cord gripping performance.
Strip conductor insulation to the length indicated in Table T1.
1. Fully insert the stripped conductor and its wiring lug (for conductors below 2.5mm²) into the contact hole;
2. Crimp the contact with a KNIPEX crimping tool P/Nº 61CA500 or a GREENLEE crimping tool P/Nº 45505. Use the 4mm² footprint whatever the conductor cross-section. Perform a double crimping with a 90º rotation, in compliance with IEC 60352-2;
2A. Conductors can also be soldered: using tin solder and a 50W soldering iron, heat the terminal for approximately 30s while heating, apply the soldering wire into the hole at the bottom of the terminal and let it penetrate by capillarity action. Let it cool down without mechanical stress;
3. Before wiring, equip each conductor with a heat-shrink sleeve or an insulating sleeve (bag of 13 pieces P/Nº 61CA083). Sleeving piliers (P/Nº 61CA400) are required to slip the insulating sleeve over the conductor;
4. Slide the insulating sleeve up to the shoulder of the contact;
4A. Slide the heat-shrink sleeve up to the shoulder of the contact. With a heat gun, apply heat evenly 360º around the sleeve until it shrinks around the terminal and wire.
See Figure F1
A: Conductor
B: Insulating Sleeve or Heat-Shrink Sleeve
C: Contact
Earthing (Grounding)
If necessary, crimp the supplied Earth (Ground) conductor in the Earth (Ground) contact.
Contact Assembly / Disassembly (See Figure F2)
Once wired, contacts must be inserted through the rear of the interior moulding (1). Push each contact fully home. Check its proper engagement by a light pull (2). Contacts can be removed with the supplied tool: insert the tool through the front (3) and push fully home (4).
Figure F2
C: Contact
D: Insulator
E: Tool
Keyings
When 2 contacts are not used according to Table T2, nine keyings can be achieved by blanking two contact holes – socket-outlet/connector side – with two caps (supplied).
Operation
| Category | ATEX Plugs, Sockets & Connectors |
|---|
| Rated Current (with wiring according to standard) | 10A |
| Maximum Voltage | 230V |
| Number of Contacts | 36P+E |
| IP Protection Lid Closed | IP66/IP67 |
| IP Protection Connected Plug | IP66/IP67 |
| Shock Resistance | IK09 |
| Ambient Temperature | -40ºC to +55ºC |
| Flexible Wiring (Min-Max) | 1mm² – 2.5mm² |
| Wiring | Crimping |
| Keying Positions | 3 |
| Protection Mode | e or i |
| ATEX Zones | 1 & 2, 21 & 22 |
Tell us your quantity and requirements — we reply within one business day.
ATEX Plugs, Sockets & ConnectorsProduct Code: 2514015
ATEX Plugs, Sockets & ConnectorsProduct Code: 2518013
The range of ATEX Plugs according to – the section outlines the complete range of hazardous area plugs and sockets certified by ATEX to the Ex e Explosion Proof explosion protection concept.
Share your specifications and quantities. Our team will review your request and come back with sourcing options and a quotation.