These medium voltage cables are used in energy supply between power distrubution systems to end users. They are used in industries like airports, wind-farms and others as power cable. They can be used free-hanging, in tubes and channels or laid underground. These cables can be used as connection power cables in transformer sabstations.
| Rated voltage | 3,6/6 kV – 6/10 kV – 8,7/15 kV – 12/20 kV (U0/U) |
|---|---|
| Conductor | Electrolytic, stranded, annealed copper wires, Class 2 (tinned conductor on request) |
| Insulation | Rubber based HEPR compound, type G7 (IEC 60502-2, HD 620 S2 P.1) |
| Sheath | Flame retardant PVC compound, Rz type (IEC 60502-2, HD 620 S2 P.1) |
| Operating temperature | -15°C to +90°C |
| Conductor screen | Extruded inner semiconductive layer |
| Conductor screen | Extruded outer semiconductive layer (strippable) |
| Screen | Overall concentric lay of copper wires and copper tape |
| Inner covering | PVC compound (only for multicores) |
| Color | Red |
| AC test voltage | 11 kV / 17 kV / 24 kV / 29 kV |
| Conductor short-circuit temp. | 250°C (Max. 5 sec) |
| Min. installation temp. | 0°C; MIN. BENDING RADIUS (during Installation) |
| Single core cables | 15x Outer Diameter |
| Multi core cables | 12x Outer Diameter |
| Current carrying capacities | In compliance with CEI 20-21, VDE 0298-4 Tab. 15, IEC 60287 and HD 620 S2 |
| Cross Section (mm²) | Nominal Overall Diameter (mm) | Approximate Weight (kg / km) | Min.Bending Radius (fixed installation) (mm) | Max. Resistance of Conductors at 20°C (ohm / km) |
|---|---|---|---|---|
| 3,6/6 kV | ||||
| 1×25/16 | 21,00 | 745 | 315 | 0,727 |
| 1×70/16 | 25,10 | 1220 | 377 | 0,268 |
| 1×95/16 | 26,10 | 1501 | 392 | 0,193 |
| 1×120/16 | 27,80 | 1756 | 417 | 0,153 |
| 1×150/25 | 30,50 | 2167 | 458 | 0,124 |
| 1×185/25 | 32,50 | 2572 | 488 | 0,0991 |
| 1×240/25 | 35,00 | 3131 | 525 | 0,074 |
| 1×300/25 | 37,80 | 3810 | 567 | 0,0601 |
| 1×400/35 | 41,50 | 4840 | 623 | 0,0470 |
| 1×500/35 | 45,40 | 5911 | 681 | 0,0366 |
| 3×25/16 | 43,90 | 2865 | 527 | 0,727 |
| 3×35/16 | 46,90 | 3341 | 563 | 0,524 |
| 3×50/16 | 50,00 | 3985 | 600 | 0,387 |
| 3×70/16 | 53,80 | 4885 | 646 | 0,268 |
| 3×95/16 | 58,10 | 5980 | 697 | 0,193 |
| 3×120/16 | 61,50 | 6970 | 738 | 0,153 |
| 3×150/25 | 66,50 | 8350 | 798 | 0,124 |
| 3×185/25 | 71,40 | 9920 | 857 | 0,0991 |
| 3×240/25 | 76,70 | 12056 | 920 | 0,074 |
| 3×300/25 | 82,80 | 14595 | 994 | 0,0601 |
| 3×400/35 | 90,90 | 18175 | 1091 | 0,0470 |
| 6/10 kV | ||||
| 1×25/16 | 21,80 | 775 | 327 | 0,727 |
| 1×35/16 | 23,10 | 886 | 347 | 0,524 |
| 1×50/16 | 24,40 | 1045 | 366 | 0,387 |
| 1×70/16 | 25,90 | 1255 | 389 | 0,268 |
| 1×95/16 | 27,90 | 1541 | 419 | 0,193 |
| 1×120/16 | 29,40 | 1800 | 441 | 0,153 |
| 1×150/25 | 31,30 | 2212 | 470 | 0,124 |
| 1×185/25 | 33,50 | 2625 | 503 | 0,0991 |
| 1×240/25 | 36,00 | 3210 | 540 | 0,074 |
| 1×300/25 | 38,60 | 3865 | 579 | 0,0601 |
| 1×400/35 | 42,50 | 4932 | 638 | 0,047 |
| 1×500/35 | 45,80 | 5956 | 687 | 0,0366 |
| 3×25/16 | 45,90 | 3070 | 551 | 0,727 |
| 3×35/16 | 48,90 | 3560 | 587 | 0,524 |
| 3×50/16 | 51,90 | 4200 | 623 | 0,387 |
| 3×70/16 | 55,70 | 5115 | 668 | 0,268 |
| 3×95/16 | 59,80 | 6201 | 718 | 0,193 |
| 3×120/16 | 63,40 | 7235 | 761 | 0,153 |
| 3×150/25 | 68,20 | 8601 | 818 | 0,124 |
| 3×185/25 | 73,30 | 10225 | 880 | 0,0991 |
| 3×240/25 | 78,70 | 12406 | 944 | 0,074 |
| 3×300/25 | 84,50 | 14910 | 1014 | 0,0601 |
| 3×400/35 | 93,00 | 18621 | 1116 | 0,0470 |
| 8,7/15 kV | ||||
| 1×25/16 | 24,2 | 880 | 363 | 0,727 |
| 1×35/16 | 25,5 | 995 | 383 | 0,524 |
| 1×50/16 | 27 | 1175 | 405 | 0,387 |
| 1×70/16 | 28,3 | 1377 | 425 | 0,268 |
| 1×95/16 | 30,3 | 1671 | 455 | 0,193 |
| 1×120/16 | 31,8 | 1935 | 477 | 0,153 |
| 1×150/25 | 33,7 | 2360 | 506 | 0,124 |
| 1×185/25 | 35,9 | 2793 | 539 | 0,0991 |
| 1×240/25 | 38,2 | 3350 | 573 | 0,074 |
| 1×300/25 | 41 | 4045 | 615 | 0,0601 |
| 1×400/35 | 45,6 | 5143 | 684 | 0,0470 |
| 1×500/35 | 48,9 | 6182 | 734 | 0,0366 |
| 3×25/16 | 50,8 | 3596 | 610 | 0,727 |
| 3×35/16 | 54,4 | 4205 | 653 | 0,524 |
| 3×50/16 | 57,4 | 4885 | 689 | 0,387 |
| 3×70/16 | 60,9 | 5795 | 731 | 0,268 |
| 3×95/16 | 65 | 6930 | 780 | 0,193 |
| 3×120/16 | 68,4 | 7970 | 821 | 0,153 |
| 3×150/25 | 73,7 | 9485 | 884 | 0,124 |
| 3×185/25 | 78,3 | 11066 | 940 | 0,0991 |
| 3×240/25 | 83,6 | 13285 | 1003 | 0,074 |
| 3×300/25 | 89,6 | 15891 | 1075 | 0,0601 |
| 12/20 kV | ||||
| 1×25/16 | 26,20 | 971 | 393 | 0,727 |
| 1×35/16 | 27,70 | 1110 | 416 | 0,524 |
| 1×50/16 | 29,00 | 1275 | 435 | 0,387 |
| 1×70/16 | 30,50 | 1500 | 458 | 0,268 |
| 1×95/16 | 32,30 | 1785 | 485 | 0,193 |
| 1×120/16 | 34,00 | 2071 | 510 | 0,153 |
| 1×150/25 | 35,90 | 2502 | 539 | 0,124 |
| 1×185/25 | 37,90 | 2930 | 569 | 0,0991 |
| 1×240/25 | 40,40 | 3512 | 606 | 0,074 |
| 1×300/25 | 43,20 | 4220 | 648 | 0,0601 |
| 1×400/35 | 47,60 | 5311 | 714 | 0,047 |
| 1×500/35 | 50,90 | 6362 | 764 | 0,0366 |
| 3×35/16 | 58,90 | 7080 | 707 | 0,527 |
| 3×50/16 | 62,00 | 7950 | 744 | 0,387 |
| 3×70/16 | 65,40 | 9045 | 785 | 0,268 |
| 3×95/16 | 69,70 | 10451 | 836 | 0,193 |
| 3×120/16 | 73,50 | 11775 | 882 | 0,153 |
| 3×150/25 | 78,30 | 15420 | 940 | 0,124 |
| 3×185/25 | 83,00 | 17425 | 996 | 0,074 |
| 3×240/25 | 88,30 | 20115 | 1060 | 0,0601 |
| 3×300/25 | 94,80 | 23386 | 1138 | 0,047 |
Tell us your quantity and requirements — we reply within one business day.
Industrial CablesFixed installation for power, control and lighting in both and safe areas applications.
Industrial Cables3GKW MM Flex Industrial Cable for industrial applications. Construction: Tinned fine copper strands (class 5 acc. to IEC 60228); Cross-linked elastomeric special compound; Cross-linked elastomeric special compound.
Industrial Cables3GKW M Industrial Cable for industrial applications. Construction: Electrolytic tinned, class 5 stranded copper wires (Iec 60228); Halogen‐free. heat resistant. cross‐linked elastomeric special compound (Requirements based on type El 109…
Share your specifications and quantities. Our team will review your request and come back with sourcing options and a quotation.