RG7H1R / RG7H1OR Industrial Cable

These medium voltage cables are used in energy supply between power distrubution systems to end users. They are used in industries like airports, wind-farms and others as power cable. They…

Rated voltage3,6/6 kV – 6/10 kV – 8,7/15 kV – 12/20 kV (U0/U)
ConductorElectrolytic, stranded, annealed copper wires, Class 2 (tinned conductor on request)
InsulationRubber based HEPR compound, type G7 (IEC 60502-2, HD 620 S2 P.1)
SheathFlame retardant PVC compound, Rz type (IEC 60502-2, HD 620 S2 P.1)
  • Quoted to your quantity
  • Documentation on request
  • International delivery

Product Overview

These medium voltage cables are used in energy supply between power distrubution systems to end users. They are used in industries like airports, wind-farms and others as power cable. They can be used free-hanging, in tubes and channels or laid underground. These cables can be used as connection power cables in transformer sabstations.

Technical Specifications

Rated voltage3,6/6 kV – 6/10 kV – 8,7/15 kV – 12/20 kV (U0/U)
ConductorElectrolytic, stranded, annealed copper wires, Class 2 (tinned conductor on request)
InsulationRubber based HEPR compound, type G7 (IEC 60502-2, HD 620 S2 P.1)
SheathFlame retardant PVC compound, Rz type (IEC 60502-2, HD 620 S2 P.1)
Operating temperature-15°C to +90°C
Conductor screenExtruded inner semiconductive layer
Conductor screenExtruded outer semiconductive layer (strippable)
ScreenOverall concentric lay of copper wires and copper tape
Inner coveringPVC compound (only for multicores)
ColorRed
AC test voltage11 kV / 17 kV / 24 kV / 29 kV
Conductor short-circuit temp.250°C (Max. 5 sec)
Min. installation temp.0°C; MIN. BENDING RADIUS (during Installation)
Single core cables15x Outer Diameter
Multi core cables12x Outer Diameter
Current carrying capacitiesIn compliance with CEI 20-21, VDE 0298-4 Tab. 15, IEC 60287 and HD 620 S2
Cross Section (mm²)Nominal Overall Diameter (mm)Approximate Weight (kg / km)Min.Bending Radius (fixed installation) (mm)Max. Resistance of Conductors at 20°C (ohm / km)
3,6/6 kV
1×25/1621,007453150,727
1×70/1625,1012203770,268
1×95/1626,1015013920,193
1×120/1627,8017564170,153
1×150/2530,5021674580,124
1×185/2532,5025724880,0991
1×240/2535,0031315250,074
1×300/2537,8038105670,0601
1×400/3541,5048406230,0470
1×500/3545,4059116810,0366
3×25/1643,9028655270,727
3×35/1646,9033415630,524
3×50/1650,0039856000,387
3×70/1653,8048856460,268
3×95/1658,1059806970,193
3×120/1661,5069707380,153
3×150/2566,5083507980,124
3×185/2571,4099208570,0991
3×240/2576,70120569200,074
3×300/2582,80145959940,0601
3×400/3590,901817510910,0470
6/10 kV
1×25/1621,807753270,727
1×35/1623,108863470,524
1×50/1624,4010453660,387
1×70/1625,9012553890,268
1×95/1627,9015414190,193
1×120/1629,4018004410,153
1×150/2531,3022124700,124
1×185/2533,5026255030,0991
1×240/2536,0032105400,074
1×300/2538,6038655790,0601
1×400/3542,5049326380,047
1×500/3545,8059566870,0366
3×25/1645,9030705510,727
3×35/1648,9035605870,524
3×50/1651,9042006230,387
3×70/1655,7051156680,268
3×95/1659,8062017180,193
3×120/1663,4072357610,153
3×150/2568,2086018180,124
3×185/2573,30102258800,0991
3×240/2578,70124069440,074
3×300/2584,501491010140,0601
3×400/3593,001862111160,0470
8,7/15 kV
1×25/1624,28803630,727
1×35/1625,59953830,524
1×50/162711754050,387
1×70/1628,313774250,268
1×95/1630,316714550,193
1×120/1631,819354770,153
1×150/2533,723605060,124
1×185/2535,927935390,0991
1×240/2538,233505730,074
1×300/254140456150,0601
1×400/3545,651436840,0470
1×500/3548,961827340,0366
3×25/1650,835966100,727
3×35/1654,442056530,524
3×50/1657,448856890,387
3×70/1660,957957310,268
3×95/166569307800,193
3×120/1668,479708210,153
3×150/2573,794858840,124
3×185/2578,3110669400,0991
3×240/2583,61328510030,074
3×300/2589,61589110750,0601
12/20 kV
1×25/1626,209713930,727
1×35/1627,7011104160,524
1×50/1629,0012754350,387
1×70/1630,5015004580,268
1×95/1632,3017854850,193
1×120/1634,0020715100,153
1×150/2535,9025025390,124
1×185/2537,9029305690,0991
1×240/2540,4035126060,074
1×300/2543,2042206480,0601
1×400/3547,6053117140,047
1×500/3550,9063627640,0366
3×35/1658,9070807070,527
3×50/1662,0079507440,387
3×70/1665,4090457850,268
3×95/1669,70104518360,193
3×120/1673,50117758820,153
3×150/2578,30154209400,124
3×185/2583,00174259960,074
3×240/2588,302011510600,0601
3×300/2594,802338611380,047

Features

  • Electromagnetic compatibility
  • Flame retardant
  • Weather resistant

Request Information About This Product

Tell us your quantity and requirements — we reply within one business day.

Related Products

3GKW M Industrial CableIndustrial Cables
Cables

3GKW M Industrial Cable

3GKW M Industrial Cable for industrial applications. Construction: Electrolytic tinned, class 5 stranded copper wires (Iec 60228); Halogen‐free. heat resistant. cross‐linked elastomeric special compound (Requirements based on type El 109…

0,6/1 kV · -40°.C … +120°.C

Have a product requirement?

Share your specifications and quantities. Our team will review your request and come back with sourcing options and a quotation.