ATEX Heat Tracing | Hazardous Area Zones 1 & 2 (21 & 22)ATEX Heat Tracing | Eltherm ELSR-N-40-2-BO Self Regulating Heating Cable
Eltherm ELSR-N-40-2-BO Self-Regulating Heating Cable

ATEX Trace Heating Cable | Eltherm ELSR-SH
ATEX Trace Heating Cable | Eltherm ELSR-SH
The Eltherm ELSR-SH high temperature self-regulating trace heating cables is designed for temperature maintenance in industrial processes and applications in hazardous areas – and is suitable for use up to 250 °C . The high chemical resistance allows the cables to be installed in environments with exposure to aggressive influences. With IECEx and ATEX Certification, Eltherm ELSR-SH trace heating cables are suitable for Zone 1 and Zone 2 hazardous areas – and have a temperature Class of T3/T2.
The self-regulating trace heating cable provides frost protection and temperature maintenance to pipework, silos vessels ,tanks, valves and pumps. Suitable for use in the following industries:
Our Team of Trained Sales Engineers are available to advise and support your ATEX trace heating enquiries – this includes design and supply of complex multi-kilometre, major-project systems to custom heat trace cable kits for the protection of winterisation against plant and factory facilities.
Eltherm ELSR-SH Heater Cable wattages per metre at 10°C – 15, 35, 45, 75 and 90 watts.
Eltherm ELSR-SH self-regulating heater cables has a BOT cable design which has a high chemical resistance and is able to withstand aggressive chemicals, oil and fuel for improved service life due to the protective braid and fluoropolymer outer jacket.
The ELSR-SH hazardous area trace heating cable has both ATEX and IECEx approvals suitable for use in Zone 1 and Zone 2 hazardous areas.
Trace Heater Classification:
System Classification:
Hazardous Area Certification:
Temperature Class: T3/T2
*Except for 90 W/m: T2
The Eltherm ELSR-SH high temperature trace heating range is designed for temperature maintenance in industrial processes and applications in hazardous areas. The trace heaters’ high chemical resistance allows them to be installed in environments with exposure to aggressive influences.
Contact our team for technical guidance, heat loss calculations for pipework systems and optimum specification of the correct trace heater cable for your application.
*1 Heating circuit lengths on the following conditions:
A Trace Heater
B Power Connection Kit
C End Termination Kit
D Junction Box
E Pipe Mounting Bracket
F Fasteners and Self-adhesive Tapes, Foils
G Insulation Bushing
H Warning Sign
I Temperature Controller
J Temperature Sensor
| Category | Heat Tracing Cables & Systems |
|---|
| Eltherm ELSR-SH Heater Cable | Nominal Output | Cable Dimensions Approx. (mm) | Cable Weight Approx. (g/m) |
| ELSR-SH-15-2-BOT | 15 W/m at 10ºC | 14 x 5.4 | 146 |
| ELSR-SH-35-2-BOT | 35 W/m at 10ºC | 14 x 5.4 | 146 |
| ELSR-SH-45-2-BOT | 45 W/m at 10ºC | 14 x 5.4 | 146 |
| ELSR-SH-75-2-BOT | 75 W/m at 10ºC | 14 x 5.4 | 146 |
| ELSR-SH-90-2-BOT | 90 W/m at 10ºC | 14 x 5.4 | 146 |
| Switch on temperature [°C] | Nominal fuse rating [A] | Heating circuit length*1 [m] | ||||
| ELSR-SH15-2-BOT | ELSR-SH35-2-BOT | ELSR-SH45-2-BOT | ELSR-SH75-2-BOT | ELSR-SH90-2-BOT | ||
| 10 | 10 | 113.0 | 50.0 | 36.0 | 18.0 | 17.0 |
| 16 | 172.0 | 80.0 | 58.0 | 30.0 | 27.0 | |
| 20 | 172.0 | 99.0 | 72.0 | 37.0 | 34.0 | |
| 25 | 172.0 | 107.0 | 90.0 | 47.0 | 42.0 | |
| 32 | 172.0 | 107.0 | 98.0 | 60.0 | 54.0 | |
| 40 | 172.0 | 107.0 | 98.0 | 73.0 | 68.0 | |
| 0 | 10 | 106.0 | 47.0 | 34.0 | 17.0 | 16.0 |
| 16 | 169.0 | 75.0 | 55.0 | 28.0 | 26.0 | |
| 20 | 172.0 | 94.0 | 69.0 | 35.0 | 32.0 | |
| 25 | 172.0 | 107.0 | 86.0 | 44.0 | 40.0 | |
| 32 | 172.0 | 107.0 | 98.0 | 57.0 | 52.0 | |
| 40 | 172.0 | 107.0 | 98.0 | 71.0 | 64.0 | |
| -10 | 10 | 99.0 | 44.0 | 32.0 | 16.0 | 15.0 |
| 16 | 159.00 | 71.0 | 52.0 | 26.0 | 25.0 | |
| 20 | 172.00 | 89.0 | 65.0 | 33.0 | 31.0 | |
| 25 | 172.00 | 107.0 | 81.0 | 41.0 | 38.0 | |
| 32 | 172.00 | 107.0 | 98.0 | 53.0 | 50.0 | |
| 40 | 172.00 | 107.0 | 98.0 | 66.0 | 62.0 | |
| -20 | 10 | 94.0 | 42.0 | 30.0 | 15.0 | 15.0 |
| 16 | 150.0 | 67.0 | 48.0 | 25.0 | 24.0 | |
| 20 | 172.0 | 84.0 | 60.0 | 31.0 | 30.0 | |
| 25 | 172.0 | 105.0 | 75.0 | 38.0 | 37.0 | |
| 32 | 172.0 | 107.5 | 96.0 | 50.0 | 48.0 | |
| 40 | 172.0 | 107.5 | 98.0 | 62.0 | 60.0 | |
| -30 | 10 | 89.0 | 40.0 | 27.5 | 15.0 | 14.0 |
| 16 | 142.0 | 64.0 | 44.0 | 24.0 | 23.0 | |
| 20 | 172.0 | 80.0 | 55.0 | 30.0 | 29.0 | |
| 25 | 172.0 | 100.0 | 68.75 | 37.0 | 36.0 | |
| 32 | 172.0 | 107.5 | 88.0 | 48.0 | 46.0 | |
| 40 | 172.0 | 107.5 | 98.0 | 60.0 | 58.0 | |
| -40 | 10 | 84.0 | 38.0 | 25.0 | 14.0 | 14.0 |
| 16 | 135.0 | 61.0 | 40.0 | 22.0 | 22.0 | |
| 20 | 169.0 | 76.0 | 50.0 | 28.0 | 28.0 | |
| 25 | 172.0 | 95.0 | 62.5 | 35.0 | 35.0 | |
| 32 | 172.0 | 107.5 | 80.0 | 45.0 | 44.0 | |
| 40 | 172.0 | 107.5 | 98.0 | 56.0 | 56.0 | |
Tell us your quantity and requirements — we reply within one business day.
ATEX Heat Tracing | Hazardous Area Zones 1 & 2 (21 & 22)Eltherm ELSR-N-40-2-BO Self-Regulating Heating Cable
ATEX Heat Tracing | Hazardous Area Zones 1 & 2 (21 & 22)ELSR-N-40-2-AO Self-Regulating Heating Cable
ATEX Heat Tracing | Hazardous Area Zones 1 & 2 (21 & 22)ELSR-N-30-2-AO Self-Regulating Heating Cable
Share your specifications and quantities. Our team will review your request and come back with sourcing options and a quotation.