MI Heating Cables – Mineral Insulated Heat Tracing Cables

TRM design and manufacture a range of bespoke heat tracing cables specialising in MI Heating Cables for high temperature and hazardous location environments. Offering a wide range of mineral insulated (MI) trace…

CategoryHeat Tracing Cables & Systems
  • Quoted to your quantity
  • Documentation on request
  • International delivery

Product Overview

MI Heating Cables

TRM design and manufacture a range of bespoke heat tracing cables specialising in MI Heating Cables for high temperature and hazardous location environments. Offering a wide range of mineral insulated (MI) trace heating cables in both single and twin conductor configurations ensuring a cost effective pipe heating solution.

Almost all applications are suited to the standard range of commercial and industrial MI Cable for trace heating.

MI Cable Types

  • Stainless Steel MI Cable Sheaths
  • Cupro-Nickel MI Cable Sheath
  • Copper MI Cable Sheath
  • Alloy 825 MI Cable Sheath
  • Inconel 600 MI Cable Sheath

Stainless Steel Sheathed MI Trace Heating Cables

Stainless steel MI trace heating cables offer high levels of corrosion protection and welding performance as well as an increased upper temperature operation to 600°C.

Cupro-Nickel Sheathed MI Trace Heating Cables

Cupro-Nickel MI trace heating cables offer high levels of corrosion protection and temperatures to seawater, chloride and sulphide stress corrosion and can reach as high as 400°C and resistances are from 0.004 ohms/m up to 1.6 ohms/m.

Copper Sheathed MI Trace Heating Cables

Copper trace heating MI cable allow good heat conduction and high resistance to corrosion in applications in marine and industrial environments. It is not suitable for use with oxidising acids, halogens, sulphides and ammonia based solutions and has a working temperature limited to 250°C.

Alloy 825 Sheathed MI Trace Heating Cables

Alloy 825 MI trace heating cables are suitable for industrial frost protection and high temperature process maintenance where good levels of corrosion resistance is required. It is not recommended for prolonged exposure between 550 and 750°C as phase transformation affects mechanical properties and consequent corrosion resistance of the alloy.

Inconel 600 Sheathed MI Trace Heating Cables

Inconel 600 MI trace heating cables offer excellent oxidation resistance and a strength at very high temperatures (up to 1150 °C). Not recommended for in sulphur atmospheres higher than 550 °C.

Mineral Insulated MI Heating Cable Applications

  • Trace Heating – Frost Protection
  • Trace Heating – Process Temperature Maintenance
  • Trace Heating – Hot Water Maintenance
  • Leak Detection Systems

Industries

  • Oil & Gas
  • Petrochemical
  • Nuclear
  • Power Generation
  • Construction
  • Automotive
  • Waste – Incineration Plants
  • Pharmaceutical
  • Refrigeration
  • Transport
  • General Engineering
  • Water

Trace Heating Systems & Heat Trace Cables

Electric heat tracing is a cable based system used to maintain, raise temperature and protect process pipework and vessels against freezing temperatures and associated frost damage – heat tracing cables mitigate and counteract cold weather effects as part of a Winterization strategy for industrial and process applications against low (sub-zero) ambient temperatures on both onshore and offshore locations.

Heat tracing systems utilising self-regulating, constant wattage and mineral insulated (MI Cable) heating cables are available to provide the optimum electrical heating system for your application – we provide a trace heating system design service.

Heat Trace Cables: Ramp Heating | Roof & Gutter Heating | Water Pipework Frost Protection | Hopper Heating | Tank Heating | Hazardous Area Heating | Fire Escapes

Technical Specifications

CategoryHeat Tracing Cables & Systems
Stainless Steel Single Core Trace Heating MI Cables Part NumberOverall Diameter mmConductor Resistance Ω/m @20°CRecommended Cold lead-in
ReferenceOD mm
H321A10K3.210.00W321-C2.5-750V5.3
H321A63003.26.30W321-C2.5-750V5.3
H321A40003.24.00W321-C2.5-750V5.3
H321A25003.42.50W321-C2.5-750V5.3
H321A16003.61.60W321-C2.5-750V5.3
H321A10003.91.00W321-C2.5-750V5.3
H321A6304.30.63W321-C2.5-750V5.3
H321A4004.70.40W321-C2.5-750V5.3
H321A2505.30.25W321-C6.0-750V6.4
H321A1606.50.16W321-C6.0-750V6.4
Cupro-Nickel (70:30) Sheathed Trace Heating MI Cables Part NumberOverall Diameter mmConductor Resistance Ω/m @20°C
H400B16003.21.60
H400B10003.41.00
H400B6303.70.63
H400B4004.00.40
H400B2504.40.25
H400B1604.90.16
H400C633.20.063
H400C403.40.040
H400C253.70.025
H400C174.60.017
H400C114.90.011
H400C75.30.007
H400C45.90.004
Copper Sheathed Single Core Heating MI Cables – Bare and HDPE Covered
Cable Reference BareCable Reference HDPE CoveredOverall Diameter mmConductor Resistance Ω/m @20°CRecommended Cold lead-in
ReferenceOD mm
H122D2000H122D2000HDPE2.82.000W122-C2.5-750V5.3
H122D1250H122D1250HDPE2.81.250W122-C2.5-750V5.3
H122D800H122D800HDPE3.50.800W122-C2.5-750V5.3
H122D630H122D630HDPE4.00.630W122-C2.5-750V5.3
H122D450H122D450HDPE4.00.450W122-C2.5-750V5.3
H122D315H122D315HDPE4.30.315W122-C2.5-750V5.3
H122D220H122D220HDPE4.50.220W122-C2.5-750V5.3
H122D140H122D140HDPE4.90.140W122-C2.5-750V5.3
H122D100H122D100HDPE5.20.100W122-C2.5-750V5.3
H122C63H122C63HDPE3.20.063W122-C2.5-750V5.3
H122C40H122C40HDPE3.40.040W122-C2.5-750V5.3
H122C25H122C25HDPE3.70.025W122-C6.0-750V6.4
H122C17H122C17HDPE4.60.017W122-C6.0-750V6.4
H122C11H122C11HDPE4.90.011W122-C6.0-750V6.4
H122C7H122C7HDPE5.30.007W122-C10.0-750V7.3
H122C4H122C4HDPE5.90.004W122-C16.0-750V8.3
Alloy 825 Single Core Heat Trace MI Cables Part NumberOverall Diameter mmConductor Resistance Ω/m @20°CRecommended Cold lead-in
ReferenceOD mm
H825A10K3.210.00W321-C2.5-750V5.3
H825A63003.26.30W321-C2.5-750V5.3
H825A40003.24.00W321-C2.5-750V5.3
H825A25003.42.50W321-C2.5-750V5.3
H825A16003.61.60W321-C2.5-750V5.3
H825A10003.91.00W321-C2.5-750V5.3
H825A6304.30.63W321-C2.5-750V5.3
H825A4004.70.40W321-C2.5-750V5.3
H825A2505.30.25W321-C6.0-750V6.4
H825A1606.50.16W321-C6.0-750V6.4
Inconel Single Core Heat Tracing MI Cables Part NumberOverall Diameter mmConductor Resistance Ω/m @20°CRecommended Cold lead-in
ReferenceOD mm
H600A10k3.210.00W321-C2.5-750V5.3
H600A63003.26.30W321-C2.5-750V5.3
H600A40003.24.00W321-C2.5-750V5.3
H600A25003.42.50W321-C2.5-750V5.3
H600A16003.61.60W321-C2.5-750V5.3
H600A10003.91.00W321-C2.5-750V5.3
H600A6304.30.63W321-C2.5-750V5.3
H600A4004.70.40W321-C2.5-750V5.3
H600A2505.30.25W321-C6.0-750V6.4
H600A1606.50.16W321-C6.0-750V6.4

Request Information About This Product

Tell us your quantity and requirements — we reply within one business day.

Related Products

Have a product requirement?

Share your specifications and quantities. Our team will review your request and come back with sourcing options and a quotation.